Genset fuel consumption: litres per hour and the real cost of low load

A catalogue figure of 200 g/kWh and real litres per hour are different things. Here is how to convert one into the other, how consumption changes with load and what running at 25 % costs.

Conversion

L/h = P × g / (1000 × ρ), with P the shaft power in kW, g the specific consumption in g/kWh and ρ the diesel density, about 0.84 kg/L. Example: 100 kW × 0.75 × 220 g/kWh ÷ 1000 ÷ 0.84 ≈ 19.6 L/h.

Real data: Cummins KTA50-GS8 (50 Hz, prime)

LoadShaft kWL/hg/kWh (shaft)L per kWh electric
100 %1 287309≈ 2020.258
75 %965238≈ 2070.264
50 %644167≈ 2180.278
25 %32288≈ 2300.293

Litres per hour come from the datasheet; grams and litres per kWh are calculated (density 0.84, set output 1 200 kW). Hourly consumption falls almost in proportion to load, but consumption per kWh rises: about 14 % more at 25 % load and 8 % more at 50 %.

What it costs

A 1 200 kW set at 50 % load for 8 000 h/year burns about 1.34 million litres. At an assumed 60 RUB/L (use your own price) that is about 80 million RUB a year, and the 8 % penalty is about 6 million RUB. Long low-load running also tends to cause carbon build-up; check the minimum load with the engine maker. Consider several smaller sets in parallel.

How to calculate for your project

  1. Take the 25/50/75/100 % table of the right rating from the datasheet.
  2. Split the year by load zone from your load profile.
  3. Multiply hours by L/h and add up.
  4. Add start-up and idle time.
  5. Size the tank: 24 h at 75 % of the set above needs about 5 700 L (238 L/h × 24 h).

Standby (ESP) uses more per hour than prime: 345 versus 309 L/h on KTA50-GS8. Typical specific consumption by engine: MaK M 32 about 177 g/kWh, Hyundai H25/33 180–181, Kolomna D49 about 198. See also sizing guide.