Paralleling gensets: synchronising, load sharing and protection
Several sets on one bus give redundancy, flexibility and fuel savings at low load — but only if strict conditions are met, otherwise the result is a short circuit or a shock to the shaft.
Four conditions to close the breaker
- Voltage — matched by the AVR;
- Frequency — matched by the speed governor;
- Phase angle — close to zero at the moment of closing;
- Phase rotation (A-B-C on both sides) — proven once at commissioning; a mismatch is an unrecoverable fault.
A synchroniser matches the first three; an independent sync-check relay (ANSI 25) blocks a bad close and must never be bypassed. With slip-frequency synchronising the incoming set is set slightly above bus frequency so it picks up a little load instead of absorbing power.
Load sharing
| Method | How it works | Pros | Cons |
|---|---|---|---|
| Droop | Frequency falls with load, typically 2–4 % from no load to full load; sets settle at a common frequency | No link between sets; unlike machines can be paralleled | Frequency drifts; all sets need identical settings |
| Isochronous | Frequency held constant; controllers share load over a link | Exact frequency, equal percentage loading | Needs a load-share link; falls back to droop if it is cut |
Example: sets of 1 000 and 500 kW with 51.5 Hz no-load frequency and 3 % droop. At 50.5 Hz both have moved 1 Hz of the 1.5 Hz range, two thirds of full load: 667 kW and 333 kW — proportional to rating, as intended. kW is shared by the governor, kvar by the AVR.
Protection
- Reverse power (ANSI 32): trips a set that is being motored by the others.
- Sync check (25): blocks closing out of window.
- Voltage, frequency, overload and short-circuit protection coordinated by the designer; settings come from the study, not from examples.
- Load shedding when a set is lost.
Common mistakes
- Different no-load frequency or droop settings.
- Bypassing the sync-check relay.
- No reverse-power protection.
- Selecting only by capacity, with no redundancy such as N+1.
Send a single-line diagram, redundancy requirement, load types and grid-parallel needs and we will propose sets from the diesel or gas catalogue. See also fuel consumption and sizing.