Paralleling gensets: synchronising, load sharing and protection

Several sets on one bus give redundancy, flexibility and fuel savings at low load — but only if strict conditions are met, otherwise the result is a short circuit or a shock to the shaft.

Four conditions to close the breaker

  1. Voltage — matched by the AVR;
  2. Frequency — matched by the speed governor;
  3. Phase angle — close to zero at the moment of closing;
  4. Phase rotation (A-B-C on both sides) — proven once at commissioning; a mismatch is an unrecoverable fault.

A synchroniser matches the first three; an independent sync-check relay (ANSI 25) blocks a bad close and must never be bypassed. With slip-frequency synchronising the incoming set is set slightly above bus frequency so it picks up a little load instead of absorbing power.

Load sharing

MethodHow it worksProsCons
DroopFrequency falls with load, typically 2–4 % from no load to full load; sets settle at a common frequencyNo link between sets; unlike machines can be paralleledFrequency drifts; all sets need identical settings
IsochronousFrequency held constant; controllers share load over a linkExact frequency, equal percentage loadingNeeds a load-share link; falls back to droop if it is cut

Example: sets of 1 000 and 500 kW with 51.5 Hz no-load frequency and 3 % droop. At 50.5 Hz both have moved 1 Hz of the 1.5 Hz range, two thirds of full load: 667 kW and 333 kW — proportional to rating, as intended. kW is shared by the governor, kvar by the AVR.

Protection

  • Reverse power (ANSI 32): trips a set that is being motored by the others.
  • Sync check (25): blocks closing out of window.
  • Voltage, frequency, overload and short-circuit protection coordinated by the designer; settings come from the study, not from examples.
  • Load shedding when a set is lost.

Common mistakes

  • Different no-load frequency or droop settings.
  • Bypassing the sync-check relay.
  • No reverse-power protection.
  • Selecting only by capacity, with no redundancy such as N+1.