How to size a genset for your load: three calculations that separate a right choice from an expensive mistake
The common mistake is to sum the loads, add 20 % and order. Do three checks instead: running load in kVA, starting of the largest motor, and the duty rating.
1. Running load in kVA, not kW
The engine limits kW, the alternator limits kVA; a set is rated at power factor 0.8, so 500 kVA gives 400 kW. Loads with different power factors must be combined as vectors.
Example, boiler house: pumps 120 kW at 0.85, ventilation 60 kW at 0.80, lighting 70 kW at 0.95, heating 50 kW at 1.0. Total 300 kW and 142 kvar gives √(300² + 142²) ≈ 332 kVA (cos φ ≈ 0.90). Dividing 300 kW by 0.8 would give 375 kVA — a margin that buys nothing.
2. Starting of the largest motor
A direct-on-line motor draws 5–7 times rated current at a power factor of about 0.4; voltage dip is usually limited to 15–20 %. In the example the largest motor is 75 kW ≈ 100 hp; at 5–6 kVA per hp it needs ≈ 500–600 kVA. With the other 225 kW running, the total at start is about 700–800 kVA. Compare against the maker's motor-starting kVA at your allowed dip, not the nameplate kVA. A soft starter (2–3× rated current) or a frequency converter often lets you drop a whole frame size.
3. Duty rating (ISO 8528-1)
| Rating | Hours per year | Load | Use |
|---|---|---|---|
| ESP — emergency standby | up to 200 h | variable, 24 h average ≤ 70 % | grid exists, set runs on outage |
| PRP — prime | unlimited | variable, average ≤ 70 %, 10 % overload 1 h in 12 | no grid or unreliable grid |
| LTP — limited time | up to 500 h | constant | peak shaving |
| COP — continuous | unlimited | constant up to 100 % | base load, CHP |
| DCP — data centre | unlimited | defined by manufacturer | data centres |
For the same set ESP is about 10 % above PRP (Baudouin 12M33G1650/5: PRP 1 200 kW, ESP 1 320 kW). Compare quotes only in the same rating. PRP average check: powers below 30 % count as 30 %, stopped time is ignored. For a 300 kW PRP set — 6 h at 240 kW, 10 h at 180 kW, 4 h at 60 kW (counted as 90 kW) — the average is (6×240 + 10×180 + 4×90)/20 = 180 kW, below the 210 kW limit.
Site conditions
Heat and altitude reduce engine output. One MTU sheet gives about 1 % per 100 m above 400 m and 3 % per 5 °C above 40 °C — about 9 % at 1 000 m and +45 °C. Use the derate table of your exact model.
What we need
A load list with power factors, the largest motor and its starting method, the duty and hours per year, the fuel, and the site altitude and temperature. Send them and we will propose options from the diesel and gas ranges.