Genset noise: decibels, enclosures, distance and neighbour complaints

A 200 kW diesel set in a weather-protective enclosure gives about 91 dB(A) at 7 m (Cummins data); with a sound-attenuated enclosure, 74–80. Here is how to read noise data and plan for a site limit.

1. Reading the numbers

  • Sound pressure level is measured with a microphone and depends on distance — "dB(A) at 1 m" or "at 7 m" in data sheets.
  • Sound power level is calculated, independent of distance, and used to compare sets and for acoustic design.
  • dB(A) weights for the ear.
  • Two identical sources add 3 dB (twice the energy); about 10 dB sounds twice as loud.

ISO 8528-10 defines airborne-noise measurement. Per Kohler, readings are taken at eight points 7 m from the set, loaded up to 100%, including exhaust. Always ask at what distance, load and silencer a figure is quoted.

2. What enclosures do

Cummins data for diesel sets of 10–1,000 kW, full load at 7 m, steel enclosures:

VersiondB(A) at 7 m
Weather-protective78–96 depending on model
Sound-attenuated Level I70–89
Level II63–78
Level III68–70

Examples: 200 kW (DGFC) — 91 weather-protective, 80 Level I, 74 Level II; 100 kW (DSGAA) — 87 and 73. Level II cuts 14–17 dB against weather-protective in these examples. For the Cummins C275D5 enclosed, the data sheet gives 77.7–78.6 dB(A) at 1 m and about 60 at 15 m. Use the sheet for your exact model. In the Waukesha P48GSI calculation sheet, exhaust noise (112 dB(A)) is listed separately from engine noise (98), so specify the silencer type in your request.

3. Distance

In a free field, level falls 6 dB per doubling of distance: 75 dB(A) at 7 m is about 69 at 14 m and 63 at 28 m. Walls, ground and wind change this, and several sets add +3 dB per doubling of their number. An acoustician should do the project calculation.

4. Russian limits

SanPiN 1.2.3685-21, table 5.35, sets noise limits for residential and public buildings and residential territory. For reference, constant noise in apartment rooms is limited to 40 dBA by day and 30 at night; for engineering equipment the limits are 5 dBA lower. Limits depend on the site purpose and time of day, and per ConsultantPlus the rules are valid until 1 March 2027, so check the current text with your designer. The task is usually stated as "no more than X dBA at the site boundary at night".

5. On a project

  1. Get the allowed level at the boundary or nearest window, day and night.
  2. Define the duty: standby sets run rarely (test runs by day); prime sets run round the clock.
  3. Take data-sheet noise at 7 m, full load, with the chosen enclosure, and apply distance attenuation.
  4. Select exhaust silencer and, if needed, inlet and outlet attenuators.
  5. Allow for several sets (+3 dB per doubling) and reflections.
  6. Agree acceptance measurements per ISO 8528-10.

Send load, number of sets and the site noise limit, and we will propose an enclosure or container and request acoustic data. See also how to choose a genset and fuel systems.

FAQ
How loud is a diesel genset?

Cummins data for 10–1,000 kW sets at full load, 7 m: 78–96 dB(A) weather-protective, 63–78 dB(A) with Level II enclosure. Use the data sheet for your model.

How does noise fall with distance?

About 6 dB per doubling of distance in a free field; two identical sources add 3 dB. Real sites need an acoustic calculation.

Which standard defines genset noise measurement?

ISO 8528-10: sound level measured at 7 m at several points under load, including exhaust.