Load module LEVRUS - NM-750kW-380V-3-K
Composition and characteristics of the load bank equipment LEVRUS - NM-750kW-380 V-3-K | ||
Equipment name | Load bank module LEVRUS - NM-750kW-380 V-3-K | |
Power | 750 kW | |
Rated power of steps | 15 x 50 kW; The steps can be increased or decreased smoothly or abruptly, while power can be switched on both sequentially (for example, adding 50/300/750 kW) and brought up immediately to 750 kW and reduced immediately to 50 kW — depending on the requirements of the test procedure. | |
Type of electrical load | Active-resistive load | |
Current type of the power circuit | Three-phase alternating current at 50 Hz | |
Rated voltage | ~400 V | |
Power factor, cos (ϕ) | 0.99 | |
Phase connection type | Star | |
Operating mode | Continuous | |
Ambient air temperature during operation of the load bank module | -25...+35 °C | |
Emergency protection | Full protection: -overheat protection; -fan failure protection; -airflow protection (AFP) and RCD; -short-circuit protection; -emergency stop button. | |
Forced air cooling | Three-phase axial fan powered from the source under test. | |
Cooling air flow direction | Horizontal | |
Control system | Built-in control panel. The control cabinet panel is intended for manual control of the load bank module and indication of operating and emergency modes. | |
Recording of electrical operating parameters | Digital three-phase multimeter SATEC or equivalent | |
Protection degree of the switchgear / control panel | IP 54 | |
Insulation resistance | <
||
| Main |
Write to us