DC uninterruptible power supplies “Shtil” PS2410G and PS2420G are designed to provide guaranteed 24 V DC power supply to various types of devices that are sensitive to mains quality:
- security and fire alarm systems;
- video surveillance equipment;
- access control equipment for restricted areas;
- intercoms and electric code locks;
- switches, routers and other components of data transmission systems.
The presented models differ in maximum output current:
- 10 A for the PS2410G UPS;
- 20 A for the PS2420G UPS;
When choosing a UPS model, it is necessary to take into account that the specified output current must provide both load power and battery charging.
Design (type “G”)
In terms of design, the products are made as a floor/desktop module with a compartment for installing batteries with a capacity of up to 26 Ah.
On the front side of the UPS are located:
- MAINS circuit breaker, designed to switch the product off and on and to protect the input circuits against current;
- BATTERY circuit breaker, designed to disconnect the batteries from the load and protect the battery against current;
- MAINS LED indicator, indicating normal operation of the product and the presence of mains supply voltage;
- OUTPUT LED indicator, showing the presence of output voltage;
- load and remote signalling connection terminals (“dry” contacts);
- connector for connecting the mains supply voltage.
Additionally, for the PS2410G and PS2420G models, a “cold start” option can be ordered. In this case, a START button will be located on the front panel of the product, designed to switch on the UPS with charged and connected batteries in the absence of 220 V mains voltage. To switch the product on, hold the START button for 5-15 s.
Operating principle
The Shtil PS2410G and PS2420G DC UPSs are built according to the scheme of a PWM converter of 220 V AC into 24 V DC. This operating principle makes it possible to provide the required load characteristics with minimum weight and dimensions. To comply with electromagnetic compatibility requirements, interference-suppressing input and output filters are installed in the product.
The power supplies automatically switch to battery operation when the mains voltage fails. The battery charging current limiting circuit implemented in the products and the protection against «deep» discharge allow its resource to be used in an optimal way. Automatic switching to mains operation occurs when the input voltage parameters are restored.