LEVRUS LLC offers turnkey hire of the AVTRON A34830 high-voltage load bank for outdoor installation, with qualified operators included. The load bank is manufactured in the USA (Cleveland, Ohio) and comprises three compact block modules — 3.5 MW, 4.25 MW and 4.25 MW. The modules can operate together or independently. The absence of step-up transformers significantly reduces logistics costs when relocating the load bank.
![]() |
![]() |
![]() |
Configuration and purpose
Technical specification: 12,000 kW (12 MW) / 10.5 kV.
- 2 (two) resistor banks Avtron K922AD42414 (4,250 kW);
- 1 (one) resistor bank Avtron K922AD42415 (3,500 kW).
The AVTRON A34830 load bank supplied by LEVRUS LLC is a custom-built load bank for testing medium-voltage generators at a power factor of 1.0.
Resistive element design
The K922A resistive elements are developed by Avtron — Helidyne (TM). For cooling, the resistive elements are positioned directly in the airflow. Resistance change during temperature fluctuations is minimised by using conservative power density operating modes. Cold-state resistance is compensated, and the required accuracy is maintained by dissipating the specified power. Load resistive elements are designed with a power tolerance from −0 to +5%, with a nominal value of +2.5%.
The ohmic resistance of each phase is within 3% of the average ohmic resistance of the three phases.
Rated specifications
- Dimensions of one module: 7468 × 2591 × 2997 mm;
- Weight of one module: no more than 5 tonnes;
- Voltage: 10,500 V (10.5 kV);
- Maximum power: 12 MW;
- Load step: 250 kW (2 steps), 500 kW, 1,000 kW, 2,000 kW and 4,000 kW (2 steps);
- Total primary circuit current of the K922AD42414 (4,250 kW): 234 A per phase;
- Total primary circuit current of the K922AD42415 (3,500 kW): 192 A per phase.
Hire costs are calculated individually for each specific project.