Three-phase SHTYL UPS ST33300 (300 kVA)

  • Brand: Shtil
  • Product Code: ST33300
  • Availability: Pre-order

The three-phase UPS ST33300 reliably ensures uninterrupted operation and continuously protects critical loads with a total capacity of up to 300 kVA/270 kW from unstable voltage in a 380 V network, for example:

  • computer rooms and telecommunications systems;
  • IT infrastructure of companies, offices and banks;
  • Data centres and server rooms.

The ST33300 is a robust metal cabinet housing the entire component base of the device (switching and distribution unit, control module, power modules, bypass and monitoring module).

Parallel connection of up to 6 ST33300 UPS units allows the output power of the uninterruptible power supply system to be increased in stages up to 1800 kVA, and also enables redundancy technology to be used to build highly reliable configurations with continuous operational availability.

Model ST33300 of online topology operates on the basis of advanced double conversion technology, which ensures:

  • wide mains voltage stabilisation range (228-478 V) without switching to battery power;
  • instant and seamless transfer of the load power to the battery when the mains voltage fails and back when it is restored;
  • continuous supply of the load with sinusoidal voltage of high accuracy (±1.5%);
  • maximum protection of the load from adverse effects of the mains;
  • full independence of the output voltage characteristics from the mains condition.

Connection

The busbars allow reliable connection of mission-critical electrical equipment.

Battery operation

Battery operation of the load is provided by external batteries. Modular battery racks and battery cabinets are provided for their installation. For correct selection of external batteries and accessories for their placement, please contact the specialists of the SHTYL Group plant.

The ST33300 UPS is also equipped with a built-in charger; its current is set in the range from 1 to 20% of the UPS capacity.

Control panel

Configuration and monitoring of the main operating parameters of the product are performed using the control panel. It includes an LCD display and LED indication.

The LCD display shows the input and output voltage, mains frequency, apparent and active load power, UPS load percentage of its rated power, the alarm log and other device parameters.

The LED indicators signal the status of the UPS itself and of its individual units: rectifier, batteries, bypass circuit, inverter and output.

Each UPS power module has its own control panel that allows monitoring of the module's operating parameters and status.

Protection

The ST33300 has a multi-level protection system against:

  • overload and short circuit;
  • internal overheating;
  • high-frequency mains interference and impulse overvoltages;
  • switching transients and non-linear distortion;
  • "deep" battery discharge.

The electronic bypass performs uninterrupted automatic transfer of the load power supply to the mains in the event of an overload or UPS failure.

The technical bypass allows manual transfer of the load power to the mains when the UPS needs maintenance or repair.

Monitoring tools

The UPS has USB, RS-232 ports and dry contacts for local/remote monitoring and control of the device.

An expansion board with an Ethernet interface (SNMP protocol) can also be additionally installed in the device. Please note that this expansion board is not included in the standard configuration and is purchased separately.

A web browser or the Shut Down Manager and Shtyl Device Manager programs are used for remote monitoring of the UPS operation.

  • Advantages

General specifications
Apparent power, kVA 300
Active power, kW 270
Form factor cabinet
Number of phases 3-in-3
Topology on-line (double conversion)
Input characteristics
Generator compatibility yes
Input mains type three-phase five-wire with common neutral (L1, L2, L3, N, PE)
Input power factor 0,99
Operating input voltage range, V 304-478 at 100% load, 228-304 with output power limitation
Rated input frequency, Hz 50/60
Rated input voltage, V 380/400/415
Soft start yes
Permissible input frequency range, Hz 40-70
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -10, -15, -20, -30, -40 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +10, +15, +20, +25 (default: +15)
Limiting phase/line input voltage range, V 130-275/228-478
Output characteristics
Crest factor 3:1
Output power factor 0,9
Output voltage type three-phase
Rated output frequency, Hz 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <1 with linear load, <6 with non-linear load
Rated AC output voltage, V 380/400/415 (three-phase with common neutral)
Output voltage waveform pure sine wave
Efficiency in online mode, % 95
Efficiency in battery mode, % 95
Output voltage stabilisation accuracy, % ±1.5 (0…100% unbalanced load)
Output frequency stabilisation accuracy (when operating from battery), % ±0,1
Overload capacity (when operating in on-line mode or from batteries) 110% for 1 hour, 125% for 10 minutes, 150% for 1 minute, over 150% for 200 ms
Transfer time to battery mode from ECO mode, ms synchronised transfer: 0
Efficiency in mains operation mode, % 99
Transient response <5% for step load (20%-80%-20%)
Recovery time after a transient process <30 ms for step load (0%-100%-0%)
Control panel and interfaces
Ethernet option
LCD display system information window, menu and current command window, event window
Parallel operation up to 6 pcs. (option)
RS-485 yes
Indication type LCD display and LED indication
"Dry" contacts yes
RS-232 yes
Interface for operation with a diesel generator yes
LED display rectifier indicator (REC), battery indicator (BAT), UPS bypass power indicator (BYP), inverter indicator (INV), load indicator (OUTPUT), status indicator (STATUS)
Connection
Input mains busbars
Load (output sockets) busbars
Cable entry from below
Minimum distance from the rear panel to a wall or other equipment, mm 300
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 95 (non-condensing)
Service life, years at least 12
Warranty period, months 24
Operating temperature range, °C from 0 to +40 (battery service life halves for every 10 C0 above 20 C0)
Storage temperature range, °C from -40 to +70
Input surge overvoltage, kV no more than 2 with a duration of no more than 50 ms
Mechanical characteristics
Housing colour grey
Batteries (battery packs)
Battery availability external (option)
Rated battery voltage, V 480 (±240), single-leg range: 198~288
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 12 years (depending on operating conditions)
Battery management functionality capacity calibration, tests (10-second, for a specified runtime, to full discharge), deep discharge protection, charge temperature compensation
Cold start option
External battery capacity, Ah depends on the required battery runtime
Number of external 12 V batteries, pcs. 40
Rated charge power of the built-in charger 10% of UPS capacity (selectable range: 1-20%)
Battery charge temperature compensation adjustable within the range from 0 to 5 mV/0C/cell
Battery end-of-discharge voltage, V/cell 1.65 (selectable range: 1.6-1.75) at a discharge current of 0.6 C, 1.75 (selectable range: 1.65-1.8) at a discharge current of 0.15 C; the final discharge voltage is automatically adjusted depending on the battery runtime
Battery equalisation charge voltage, V/cell 2.4 (selectable range: 2.3-2.45)
Battery float charge voltage, V/cell 2.25 (selectable range: 2.2-2.35)