The three-phase UPS ST33250 provides guaranteed protection against problems associated with poor-quality power or its sudden loss for critical loads with a total capacity of up to 250 kVA/225 kW, for example:

  • computer rooms and telecommunications systems;
  • IT infrastructure of companies, offices or banks;
  • data centres and server rooms.

The UPS component base (switching and distribution unit, control module, power modules, bypass and monitoring module) is housed in a metal cabinet with a door featuring a dust filter.

The ability to connect up to 6 ST33250 UPS units in parallel allows the output power of the uninterruptible power supply system to be increased in stages up to 1500 kVA, and also allows redundancy technology to be used to build highly reliable configurations with constant operational readiness.

The ST33250 is an online topology UPS with double energy conversion, thanks to which the following is provided:

  • wide mains voltage stabilisation range (228-478 V) without switching to battery power;
  • instant and seamless transfer of the load power to the battery when the mains voltage fails and back when it is restored;
  • continuous supply of the load with sinusoidal voltage of high accuracy (±1.5%);
  • maximum protection of the load from adverse effects of the mains;
  • full independence of the output voltage characteristics from the mains condition.

Connection

The load and mains are connected via busbars.

Battery operation

Battery operation of the load is provided by external batteries. Modular battery racks and battery cabinets are provided for their installation. For correct selection of external batteries and accessories for their placement, please contact the specialists of the SHTYL Group plant.

The ST33250 UPS is also equipped with a built-in charger; its current is set in the range from 1 to 20% of the UPS capacity.

Control panel

Configuration and monitoring of the main operating parameters of the product are performed using the control panel. It includes an LCD display and LED indication.

The LCD display shows the input and output voltage, mains frequency, apparent and active load power, UPS load percentage of its rated power, the alarm log and other device parameters.

The LED indicators signal the status of the UPS itself and of its individual units: rectifier, batteries, bypass circuit, inverter and output.

Each UPS power module has its own control panel that allows monitoring of the module's operating parameters and status.

Protection

The ST33250 is equipped with a multi-level protection system against:

  • overload and short circuit;
  • internal overheating;
  • high-frequency mains interference and impulse overvoltages;
  • switching transients and non-linear distortion;
  • "deep" battery discharge.

The model also has:

  • electronic bypass – automatically switches the load power to the mains in the event of overload or UPS failure;
  • manual bypass – used when UPS maintenance or repair is required without interrupting the load power.

Monitoring tools

The ST33250 is equipped with USB, RS-232 ports and dry contacts for local/remote monitoring and control of the device.

An Ethernet expansion card (SNMP protocol) can also be connected to the UPS. Please note that this expansion card is not included in the standard package and must be purchased separately.

A web browser or the Shut Down Manager and Shtyl Device Manager programs can be used for remote monitoring of the UPS operation.

  • Advantages

General specifications
Apparent power, kVA 250
Active power, kW 225
Form factor cabinet
Number of phases 3-in-3
Topology on-line (double conversion)
Input characteristics
Generator compatibility yes
Input mains type three-phase five-wire with common neutral (L1, L2, L3, N, PE)
Input power factor 0,99
Operating input voltage range, V 304-478 at 100% load, 228-304 with output power limitation
Rated input frequency, Hz 50/60
Rated input voltage, V 380/400/415
Soft start yes
Permissible input frequency range, Hz 40-70
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -10, -15, -20, -30, -40 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +10, +15, +20, +25 (default: +15)
Limiting phase/line input voltage range, V 130-275/228-478
Output characteristics
Crest factor 3:1
Output power factor 0,9
Output voltage type three-phase
Rated output frequency, Hz 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <1 with linear load, <6 with non-linear load
Rated AC output voltage, V 380/400/415 (three-phase with common neutral)
Output voltage waveform pure sine wave
Efficiency in online mode, % 95
Efficiency in battery mode, % 95
Output voltage stabilisation accuracy, % ±1.5 (0…100% unbalanced load)
Output frequency stabilisation accuracy (when operating from battery), % ±0,1
Overload capacity (when operating in on-line mode or from batteries) 110% for 1 hour, 125% for 10 minutes, 150% for 1 minute, over 150% for 200 ms
Transfer time to battery mode from ECO mode, ms synchronised transfer: 0
Efficiency in mains operation mode, % 99
Transient response <5% for step load (20%-80%-20%)
Recovery time after a transient process <30 ms for step load (0%-100%-0%)
Control panel and interfaces
Ethernet option
LCD display system information window, menu and current command window, event window
Parallel operation up to 6 pcs. (option)
RS-485 yes
Indication type LCD display and LED indication
"Dry" contacts yes
RS-232 yes
Interface for operation with a diesel generator yes
LED display rectifier indicator (REC), battery indicator (BAT), UPS bypass power indicator (BYP), inverter indicator (INV), load indicator (OUTPUT), status indicator (STATUS)
Connection
Input mains busbars
Load (output sockets) busbars
Cable entry from below
Minimum distance from the rear panel to a wall or other equipment, mm 300
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 95 (non-condensing)
Service life, years at least 12
Warranty period, months 24
Operating temperature range, °C from 0 to +40 (battery service life halves for every 10 C0 above 20 C0)
Storage temperature range, °C from -40 to +70
Input surge overvoltage, kV no more than 2 with a duration of no more than 50 ms
Mechanical characteristics
Housing colour grey
Batteries (battery packs)
Battery availability external (option)
Rated battery voltage, V 480 (±240), single-leg range: 198~288
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 12 years (depending on operating conditions)
Battery management functionality capacity calibration, tests (10-second, for a specified runtime, to full discharge), deep discharge protection, charge temperature compensation
Cold start option
External battery capacity, Ah depends on the required battery runtime
Number of external 12 V batteries, pcs. 40
Rated charge power of the built-in charger 10% of UPS capacity (selectable range: 1-20%)
Battery charge temperature compensation adjustable within the range from 0 to 5 mV/0C/cell
Battery end-of-discharge voltage, V/cell 1.65 (selectable range: 1.6-1.75) at a discharge current of 0.6 C, 1.75 (selectable range: 1.65-1.8) at a discharge current of 0.15 C; the final discharge voltage is automatically adjusted depending on the battery runtime
Battery equalisation charge voltage, V/cell 2.4 (selectable range: 2.3-2.45)
Battery float charge voltage, V/cell 2.25 (selectable range: 2.2-2.35)