‎+7 (499) 500-24-60
Moscow, Udaltsova St., 81, bldg 2, office 6
Three-phase UPS

Three-phase SHTYL UPS ST33040 (40 kVA)

  • Brand: Shtil
  • Product Code: ST33040
  • Availability: Pre-order

The three-phase UPS ST33040 is the optimal solution for ensuring uninterrupted operation and protecting the power supply from mains voltage fluctuations of critical three-phase and single-phase equipment with a total capacity of up to 40 kVA / 36 kW, for example:

  • telecommunications equipment and communication systems;
  • IT equipment;
  • of Hi-Tech audio equipment;
  • television equipment;
  • retail and entertainment equipment.

The ability to connect up to 6 ST33040 UPS units in parallel allows the output power of the uninterruptible power supply system to be increased in stages, as the number of consumers grows, up to 240 kVA, and makes it easier on the budget at the initial purchase stage.

The ST33040 is an online topology UPS with double conversion technology, thanks to which the device provides:

  • operation over a wide mains voltage range (228-478 V) without switching to battery power;
  • instant and seamless transfer of the load power to the battery when the mains voltage fails;
  • continuous supply of the load with sinusoidal voltage of high accuracy (±1.5%);
  • maximum protection of the load from adverse effects of the mains;
  • full independence of the output voltage characteristics from the mains condition.

Installation and connection

The ST33040 is installed on any flat horizontal surface on swivel castors. The UPS power supply and load connection are made via terminal blocks located on the rear panel of the device.

Battery operation

A special connector for external batteries and a charger allow the load to operate autonomously for the required time. The charger current is set in the range from 1 to 20% of the UPS power. For correct selection of external batteries, please contact the specialists of the SHTYL Group plant.

Control panel

Configuration and monitoring of the main operating parameters of the product are performed using the control panel. It includes an LCD display, a current path mimic diagram, LED indicators and control buttons.

The device's LCD display shows the input and output voltage, its frequency, the apparent, active and reactive load power, UPS load percentage of its rated power, remaining battery runtime, the alarm log and other device parameters.

The LED indicators signal the status of the UPS itself and of its individual units: rectifier, batteries, bypass circuit, inverter, output.

Protection

The ST33040 is equipped with a multi-level protection system against:

  • overload and short circuit;
  • internal overheating;
  • high-frequency mains interference and impulse overvoltages;
  • switching transients and non-linear distortion;
  • "deep" battery discharge.

The UPS has two types of bypass: electronic bypass – for uninterrupted automatic transfer of load power to the mains if the UPS fails or is overloaded; technical bypass – for servicing the UPS without interrupting the load power supply.

Monitoring tools

The ST33040 functionality provides remote monitoring and control of the device. For this purpose, the rear of the UPS has USB, RS-232 and RS-485 ports (Modbus RTU and Modbus ASCII protocols) and dry contacts.

An expansion card with an Ethernet interface (SNMP/HTTP/HTTPS/SSH protocols) can additionally be connected to the UPS. Please note that this expansion card is not included in the standard scope of supply and must be purchased separately.

After installing the board, the UPS operation is easily monitored in a web browser or using special software: Shut Down Manager or Shtyl Device Manager.

  • Advantages

General specifications
Apparent power, kVA 40
Active power, kW 36
Form factor floor-standing
Number of phases 3-in-3
Topology on-line (double conversion)
Input characteristics
Generator compatibility yes
Input mains type three-phase five-wire with common neutral (L1, L2, L3, N, PE)
Input power factor 0,99
Maximum input current per phase, A 70
Operating input voltage range, V 304-478 at 100% load, 228-304 with output power limitation
Rated input frequency, Hz 50/60
Rated input voltage, V 380/400/415
Soft start yes
Permissible input frequency range, Hz 40-70
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -10, -15, -20, -30, -40 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +10, +15, +20, +25 (default: +15)
Limiting phase/line input voltage range, V 130-275/228-478
Output characteristics
Crest factor 3:1
Output power factor 0,9
Output voltage type three-phase
Rated output frequency, Hz 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <1 with linear load, <6 with non-linear load
Rated AC output voltage, V 380/400/415 (three-phase with common neutral)
Output voltage waveform pure sine wave
Efficiency in online mode, % 95
Efficiency in battery mode, % 95
Output voltage stabilisation accuracy, % ±1.5 (0…100% unbalanced load)
Output frequency stabilisation accuracy (when operating from battery), % ±0,1
Overload capacity (when operating in on-line mode or from batteries) 110% for 1 hour, 125% for 10 minutes, 150% for 1 minute, over 150% for 200 ms
Transfer time to battery mode from ECO mode, ms synchronised transfer: 0
Efficiency in mains operation mode, % 99
Transient response <5% for step load (20%-80%-20%)
Recovery time after a transient process <30 ms for step load (0%-100%-0%)
Maximum output current per phase, A 60
Control panel and interfaces
Ethernet option
LCD display system information window, menu and current command window, event window
Parallel operation up to 6 pcs. (option)
RS-485 yes
"Dry" contacts yes
RS-232 yes
Function keys back, left, right, enter, EPO
Interface for operation with a diesel generator yes
LED display rectifier indicator (REC), battery indicator (BAT), UPS bypass power indicator (BYP), inverter indicator (INV), load indicator (OUTPUT), status indicator (STATUS)
Connection
Input mains busbars
Load (output sockets) busbars
Cable entry from below
Minimum distance from the rear panel to a wall or other equipment, mm 300
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 95 (non-condensing)
Service life, years at least 12
Warranty period, months 24
Operating temperature range, °C from 0 to +40 (battery service life halves for every 10 C0 above 20 C0)
Storage temperature range, °C from -40 to +70
Input surge overvoltage, kV no more than 2 with a duration of no more than 50 ms
Mechanical characteristics
Housing colour grey
Weight, kg 61
Overall dimensions HxWxD (unpacked), mm 767×250×891
Batteries (battery packs)
Battery availability external (option)
Rated battery voltage, V 480 (±240), single-leg range: 198~288
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 7 (depending on operating conditions)
Battery management functionality capacity calibration, tests (10-second, for a specified runtime, to full discharge), deep discharge protection, charge temperature compensation
Cold start option
External battery capacity, Ah depends on the required battery runtime
Number of external 12 V batteries, pcs. 40
Rated charge power of the built-in charger 10% of UPS capacity (selectable range: 1-20%)
Battery charge temperature compensation adjustable within the range from 0 to 5 mV/0C/cell
Battery end-of-discharge voltage, V/cell 1.65 (selectable range: 1.6-1.75) at a discharge current of 0.6 C, 1.75 (selectable range: 1.65-1.8) at a discharge current of 0.15 C; the final discharge voltage is automatically adjusted depending on the battery runtime
Battery equalisation charge voltage, V/cell 2.4 (selectable range: 2.3-2.45)
Battery float charge voltage, V/cell 2.25 (selectable range: 2.2-2.35)
Rated battery circuit current, A 80

Write to us

We will reply to info@levrus.ru shortly