The modular online UPS SM300 (6x30) is used to ensure uninterrupted operation and protection against unstable voltage in a 380 V network for three-phase loads, for example:
- telecommunications and server equipment;
- IT and computer equipment;
- Hi-Tech audio and video equipment;
- electrical equipment for the retail and entertainment sector;
- high-power household appliances.
The SM300 (6x30) is a robust metal cabinet housing six 30 kVA / 27 kW power modules and other components. The cabinet door has a dust filter.
Connecting additional power modules allows the output power of the power system to be increased to 300 VA /270 kW, and parallel connection of up to 3 SM300 UPS units fully equipped with modules – to 900 kVA / 810 kW.
The SM300 (6x30) also supports redundancy based on UPS modules or units to build high-reliability configurations.
The SM300 (6x30) is an online UPS featuring double-conversion technology, which provides:
- operation over a wide mains voltage range (228-478 V) without switching to battery power;
- instant and seamless transfer of the load power to the battery when the mains voltage fails and back when it is restored;
- continuous supply of the load with sinusoidal voltage of high accuracy (±2%);
- maximum protection of the load from adverse effects of the mains;
- full independence of the output voltage characteristics from the mains condition.
Hot-swap replacement of a failed power module is provided (without de-energising the UPS and the load). In this case, the load power will be distributed evenly among the operating redundant modules, if they were installed.
Connection
The load and input mains are connected via busbars.
Battery operation
Model SM300 (6x30) without built-in batteries. The device can provide long-term autonomous operation of the load by connecting external batteries. For correct selection of external batteries and solutions for their installation, please contact the specialists of the SHTYL Group plant.
The UPS has a built-in charger whose current is set in the range from 1 to 20% of the UPS power.
Control panel
A modern control panel is fitted on the UPS door, comprising an LCD display and LED indicators. They allow convenient monitoring of the device's operation and basic settings to be made.
The LCD display shows the input and output voltage, input frequency, apparent and active load power, UPS load percentage of its rated power, the alarm log and other device parameters.
The LED indicators signal the status of the UPS itself and of its individual units: rectifier, batteries, bypass circuit, inverter and output.
The power module installed inside the UPS has its own LCD display, which shows its operating parameters and allows its status to be monitored.
Protection
The SM300 (6x30) is equipped with a highly efficient protection system against:
- overload and short circuit;
- internal overheating;
- high-frequency mains interference and impulse overvoltages;
- switching transients and non-linear distortion;
- "deep" battery discharge.
The centralised electronic bypass switches the load supply to the mains without interrupting the power supply to the critical load in the event of an overload or UPS failure.
The technical bypass enables manual transfer of the load supply to the mains when repair or servicing of the UPS is required without interrupting the operation of the connected equipment.
Monitoring tools
The SM300 (6x30) supports local/remote monitoring and control.
For this purpose, dry contacts, USB and RS-232 ports, as well as an Ethernet interface supporting SNMP, SHTYL and other protocols are used.
The UPS is monitored using Shut Down Manager or Shtyl Device Manager software.
The model is also equipped with an EPO port for remote emergency shutdown.