The modular online UPS SM300 (4x30) is a professional system for ensuring high-quality power supply and uninterrupted operation of critical three-phase equipment, for example:
- computer rooms, server rooms or the entire IT infrastructure of companies;
- security systems;
- radio and television broadcasting facilities;
- telecommunications equipment;
- retail and banking equipment.
The SM300 (4x30) is a robust metal cabinet housing four 30 kVA / 27 kW power modules and other components. The cabinet door has a dust filter.
Connecting additional power modules allows the output power of the power system to be increased to 300 VA /270 kW, and parallel connection of up to 3 SM300 UPS units fully equipped with modules – to 900 kVA / 810 kW.
The SM300 (4x30) also supports module- or UPS-unit-based redundancy technologies for building high-reliability configurations.
The SM300 (4x30) is an online UPS operating on double-conversion technology, which provides:
- operation over a wide mains voltage range (228-478 V) without switching to battery power;
- instant and seamless transfer of the load power to the battery when the mains voltage fails and back when it is restored;
- continuous supply of the load with sinusoidal voltage of high accuracy (±1.5%);
- maximum protection of the load from adverse effects of the mains;
- full independence of the output voltage characteristics from the mains condition.
Hot-swap replacement of a failed power module is provided (without de-energising the UPS and the load). In this case, the load power will be distributed evenly among the operating redundant modules, if they were installed.
Connection
The load and the device's power supply are connected via busbars.
Battery operation
The SM300 (4x30) has no built-in batteries but can provide long-term autonomous load operation by connecting external batteries. For correct selection of external batteries and their installation solutions, please contact the specialists of the SHTYL Group plant.
The model is also equipped with a built-in charger; its current is set in the range from 1 to 20% of the UPS power.
Control panel
A modern control panel is fitted on the UPS door, comprising an LCD display and LED indicators. They allow convenient monitoring of the device's operation and basic settings to be made.
The LCD display shows the input and output voltage, input frequency, apparent and active load power, UPS load percentage of its rated power, the alarm log and other device parameters.
The LED indicators signal the status of the UPS itself and of its individual units: rectifier, batteries, bypass circuit, inverter and output.
The power module installed inside the UPS has its own LCD display, which shows its operating parameters and allows its status to be monitored.
Protection
The SM300 (4x30) UPS uses a multi-level protection system against:
- overload and short circuit;
- internal overheating;
- high-frequency mains interference and impulse overvoltages;
- switching transients and non-linear distortion;
- "deep" battery discharge.
The centralised electronic bypass automatically and uninterruptedly switches the load power supply to the mains in the event of an overload or UPS failure
The manual maintenance bypass helps maintain continuity of power to the critical load, for example, if the UPS requires servicing.
Monitoring tools
The SM300 (4x30) UPS provides local/remote operation monitoring.
For this purpose, dry contacts, USB and RS-232 ports, as well as an Ethernet interface supporting SNMP, SHTYL and other protocols are used.
Device operation is tracked in Shut Down Manager or Shtyl Device Manager software.
The UPS is also equipped with an EPO port for remote emergency shutdown.
- Advantages