The SM060/20 (3x20) modular online UPS is designed to ensure uninterrupted operation and reliable protection against mains voltage surges for critical three-phase loads. The model is ideally suited for electrical equipment:
- data centres, workstations and communication nodes;
- communication and security systems;
- financial and trading companies.
SM060/20 (3x20) is a robust metal cabinet housing three 20 kVA /18 kW power modules and other device components. The cabinet door has a dust filter.
The UPS also supports parallel connection of up to 3 SM060/20 UPS units, which allows an output power of up to 180 kVA/162 kW.
SM060/20 (3x20) also supports the use of redundancy technologies based on UPS modules or units to build highly reliable configurations.
SM060/20 (3x20) operates on the basis of double conversion of electricity, which provides:
- operation over a wide mains voltage range (228-478 V) without switching to battery power;
- instant and seamless transfer of the load power to the battery when the mains voltage fails and back when it is restored;
- continuous supply of the load with sinusoidal voltage of high accuracy (±1.5%);
- maximum protection of the load from adverse effects of the mains;
- full independence of the output voltage characteristics from the mains condition.
Hot-swap replacement of a failed power module is provided (without de-energising the UPS and the load). In this case, the load power will be distributed evenly among the operating redundant modules, if they were installed.
Connection
The input mains and electrical equipment are connected to the UPS via busbars.
Battery operation
SM060/20 (3x20) has no built-in batteries but is capable of providing long-term autonomous operation of the load by connecting external batteries. For the correct selection of external batteries and their installation solutions, please contact the specialists of the SHTYL Group plant.
The UPS model is equipped with a built-in charger; its current is set in the range from 1 to 20% of the UPS power.
Control panel
A modern control panel is fitted on the UPS door, comprising an LCD display and LED indicators. They allow convenient monitoring of the device's operation and basic settings to be made.
The LCD display shows the input and output voltage, input frequency, apparent and active load power, UPS load percentage of its rated power, the alarm log and other device parameters.
The LED indicators signal the status of the UPS itself and of its individual units: rectifier, batteries, bypass circuit, inverter and output.
The power module installed inside the UPS has its own LCD display, which shows its operating parameters and allows its status to be monitored.
Protection
The SM060/20 (3x20) uses a multi-level protection system against:
- overload and short circuit;
- internal overheating;
- high-frequency mains interference and impulse overvoltages;
- switching transients and non-linear distortion;
- "deep" battery discharge.
The UPS model is equipped with a centralised electronic bypass, which allows automatic and uninterrupted switching of the load power to the mains in the event of overload or failure of the device.
The built-in manual maintenance bypass is used for repair and servicing of the UPS without interrupting the load power supply.
Monitoring tools
SM060/20 (3x20) offers the ability to organise local/remote monitoring of operation.
For this purpose, dry contacts, USB and RS-232 ports, as well as an Ethernet interface supporting SNMP, SHTYL and other protocols are used.
The UPS is conveniently monitored in the Shut Down Manager or Shtyl Device Manager programs.
In addition, the device is equipped with an EPO port for remote emergency shutdown.
- Advantages