Modular three-phase UPS SHTYL SM060(2x10) 20 kVA

  • Brand: Shtil
  • Product Code: SM060-2X10
  • Availability: Pre-order

The SM060/10 (2x10) modular online UPS provides uninterrupted power supply and protects commercial and industrial three-phase electrical equipment from unstable voltage in the 380 V mains, for example:

  • telecommunications and server equipment;
  • IT and computer equipment;
  • Hi-Tech audio and video equipment;
  • electrical equipment for the retail sector.

SM060/10 (2x10) is a robust metal cabinet housing two 10 kVA /9 kW power modules and other components. The cabinet door has a dust filter.

Connecting additional power modules allows the output power of the power system to be increased to 60 kVA /54 kW, and parallel connection of up to 3 SM060/10 units fully equipped with modules – to 180 kVA / 162 kW.

SM060/10 (2x10) also supports redundancy technologies based on UPS modules or units to build highly reliable configurations.

SM060/10 (2x10) uses advanced double conversion technology, which provides:

  • operation over a wide mains voltage range (228-478 V) without switching to battery power;
  • instant and seamless transfer of the load power to the battery when the mains voltage fails and back when it is restored;
  • continuous supply of the load with sinusoidal voltage of high accuracy (±2%);
  • maximum protection of the load from adverse effects of the mains;
  • full independence of the output voltage characteristics from the mains condition.

Hot-swap replacement of a failed power module is provided (without de-energising the UPS and the load). In this case, the load power will be distributed evenly among the operating redundant modules, if they were installed.

Connection

The mains and load are connected to the UPS via busbars.

Battery operation

The SM060/10 UPS (2x10) does not have built-in batteries, but is capable of providing long-term autonomous operation of the load by connecting external batteries. For the correct selection of external batteries and solutions for their installation, please contact the specialists of the SHTYL Group plant.

The SM060/10 UPS (2x10) is also equipped with a built-in charger; its current is set in the range from 1 to 20% of the UPS power.

Control panel

A modern control panel is fitted on the UPS door, comprising an LCD display and LED indicators. They allow convenient monitoring of the device's operation and basic settings to be made.

The LCD display shows the input and output voltage, input frequency, apparent and active load power, UPS load percentage of its rated power, the alarm log and other device parameters.

The LED indicators signal the status of the UPS itself and of its individual units: rectifier, batteries, bypass circuit, inverter and output.

The power module installed inside the UPS has its own LCD display, which shows its operating parameters and allows its status to be monitored.

Protection

SM060/10 (2x10) is equipped with a built-in protection system against:

  • overload and short circuit;
  • internal overheating;
  • high-frequency mains interference and impulse overvoltages;
  • switching transients and non-linear distortion;
  • "deep" battery discharge.

The UPS is also equipped with:

  • with centralised electronic bypass, for uninterrupted automatic switching of the load power to the mains in the event of overload or UPS failure;
  • with a maintenance bypass for manually transferring the load power to the mains when it is necessary to repair or service the UPS without interrupting the load operation.

Monitoring tools

SM060/10 (2x10) has functionality for local/remote monitoring of the device's operation.

For this purpose, dry contacts, USB and RS-232 ports, as well as an Ethernet interface supporting SNMP, SHTYL and other protocols are used.

Device operation is tracked in Shut Down Manager or Shtyl Device Manager software.

The UPS is also equipped with an EPO port for remote emergency shutdown.

  • Advantages

General specifications
Apparent power, kVA 20
Active power, kW 18
Form factor cabinet (modular)
Number of phases 3-in-3
Topology on-line (double conversion)
Input characteristics
Generator compatibility yes
Input mains type three-phase five-wire with common neutral (L1, L2, L3, N, PE)
Input power factor 0,99
Operating input voltage range, V 304-478 at 100% load, 228-304 with output power limitation
Rated input frequency, Hz 50/60
Rated input voltage, V 380/400/415
Soft start yes
Permissible input frequency range, Hz 40-70
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -10, -15, -20, -30, -40 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +10, +15, +20, +25 (default: +15)
Limiting phase/line input voltage range, V 130-275/228-478
Output characteristics
Crest factor 3:1
Output power factor 0,9
Output voltage type three-phase
Rated output frequency, Hz 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <1.5 with linear load, <5 with non-linear load
Rated AC output voltage, V 380/400/415 (three-phase with common neutral)
Output voltage waveform pure sine wave
Efficiency in online mode, % 95
Efficiency in battery mode, % 95
Output voltage stabilisation accuracy, % ±1.5 (0…100% unbalanced load)
Output frequency stabilisation accuracy (when operating from battery), % ±0,1
Overload capacity (when operating in on-line mode or from batteries) 110% for 1 hour, 125% for 10 minutes, 150% for 1 minute, over 150% for 200 ms
Transfer time to battery mode from ECO mode, ms synchronised transfer: 0
Efficiency in mains operation mode, % 99
Transient response <5% for step load (20%-80%-20%)
Recovery time after a transient process <30 ms for step load (0%-100%-0%)
Control panel and interfaces
Ethernet option
LCD display colour touchscreen, system information window, menu and current command window, event window
Parallel operation up to 3 pcs. (optional)
RS-485 yes
Indication type LCD display and LED indication
"Dry" contacts yes
RS-232 yes
Interface for operation with a diesel generator yes
LED display rectifier indicator (REC), battery indicator (BAT), UPS bypass power indicator (BYP), inverter indicator (INV), load indicator (OUTPUT), status indicator (STATUS)
Connection
Input mains busbars
Load (output sockets) busbars
Cable entry from below
Minimum distance from the rear panel to a wall or other equipment, mm 300
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 95 (non-condensing)
Service life, years at least 12
Warranty period, months 24
Operating temperature range, °C from 0 to +40 (battery service life halves for every 10 C0 above 20 C0)
Storage temperature range, °C from -40 to +70
Input surge overvoltage, kV no more than 2 with a duration of no more than 50 ms
Mechanical characteristics
Housing colour grey
Overall dimensions HxWxD (unpacked), mm 1700x600x992
Batteries (battery packs)
Battery availability external (option)
Rated battery voltage, V 480 (±240), single-leg range: 198~288
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 12 years (depending on operating conditions)
Battery management functionality capacity calibration, tests (10-second, for a specified runtime, to full discharge), deep discharge protection, charge temperature compensation
Cold start yes
External battery capacity, Ah depends on the required battery runtime
Number of external 12 V batteries, pcs. 40
Rated charge power of the built-in charger 10% of UPS capacity (selectable range: 1-20%)
Battery charge temperature compensation adjustable within the range from 0 to 5 mV/0C/cell
Battery end-of-discharge voltage, V/cell 1.65 (selectable range: 1.6-1.75) at a discharge current of 0.6 C, 1.75 (selectable range: 1.65-1.8) at a discharge current of 0.15 C; the final discharge voltage is automatically adjusted depending on the battery runtime
Battery equalisation charge voltage, V/cell 2.4 (selectable range: 2.3-2.45)
Battery float charge voltage, V/cell 2.25 (selectable range: 2.2-2.35)