The SM030 (2x10) modular online UPS provides uninterrupted power supply and protects three-phase electrical equipment from unstable voltage in the 380 V mains, for example:
- telecommunications and server equipment;
- IT and computer equipment;
- Hi-Tech audio and video equipment;
- electrical equipment for the retail sector;
- high-power household electrical equipment.
SM030 (2x10) is a robust metal cabinet housing two 10 kVA /9 kW power modules and other device components. The cabinet door has a dust filter.
Connecting an additional power module allows the output power of the power system to be increased to 30 VA / 27 kW, and parallel connection of up to 3 SM030 UPS units fully equipped with modules – to 90 kVA/ 81 kW.
SM030 (2x10) also supports redundancy technologies based on UPS modules or units to build highly reliable configurations.
SM030 (2x10) uses advanced double conversion technology, which provides:
- operation over a wide mains voltage range (228-478 V) without switching to battery power;
- instant and seamless transfer of the load power to the battery when the mains voltage fails and back when it is restored;
- continuous supply of the load with sinusoidal voltage of high accuracy (±1.5%);
- maximum protection of the load from adverse effects of the mains;
- full independence of the output voltage characteristics from the mains condition.
Hot-swap replacement of a failed power module is provided (without de-energising the UPS and the load). In this case, the load power will be distributed evenly among the operating redundant modules, if they were installed.
Connection
The mains and load are connected to the UPS via busbars.
Battery operation
The SM030 UPS (2x10) does not have built-in batteries, but is capable of providing long-term autonomous operation of the load by connecting external batteries. For the correct selection of external batteries and solutions for their installation, please contact the specialists of the SHTYL Group plant.
The SM030 UPS (2x10) is also equipped with a built-in charger; its current is set in the range from 1 to 20% of the UPS power.
Control panel
A modern LCD display with LED indicators is fitted on the UPS door, allowing the device's operation to be easily monitored and basic settings to be made.
The LCD display shows the input and output voltage, input frequency, apparent and active load power, UPS load percentage of its rated power, the alarm log and other device parameters.
The LED indicators signal the status of the UPS itself and of its individual units: rectifier, batteries, bypass circuit, inverter and output.
The power module installed inside the UPS has its own LCD display, which shows its operating parameters and allows its status to be monitored.
Protection
SM030 (2x10) is equipped with a built-in protection system against:
- overload and short circuit;
- internal overheating;
- high-frequency mains interference and impulse overvoltages;
- switching transients and non-linear distortion;
- "deep" battery discharge.
The UPS is also equipped with:
- with centralised electronic bypass, allowing automatic and uninterrupted switching of the load power to the mains in the event of overload or device failure;
- with a maintenance bypass for manually transferring the load power to the mains when it is necessary to repair or service the UPS without interrupting the load operation.
Monitoring tools
SM030 (2x10) has functionality for local/remote monitoring of the device's operation.
For this purpose, dry contacts, USB and RS-232 ports, as well as an Ethernet interface supporting SNMP, SHTYL and other protocols are used.
Device operation is tracked in Shut Down Manager or Shtyl Device Manager software.
The UPS also provides an EPO port for remote emergency shutdown.