‎+7 (499) 500-24-60
Moscow, Udaltsova St., 81, bldg 2, office 6
Single-phase UPS

SHTYL SW500L UPS kit (500 VA/400 W) with battery for 1 h 45 min

  • Brand: Shtil
  • Product Code: SW500L-55Ah
  • Availability: Pre-order
67 654 ₽

The online UPS SW500L with 55 Ah batteries installed in the battery rack BS-24-1W is capable of providing autonomous operation of critical consumers with a power of up to 500 VA/400 W for 2 h (at 80% load). The battery runtime at other UPS load levels is shown on the Battery runtime tab. Examples of loads include:

  • gas boiler and circulation pump;
  • water supply and water treatment system;
  • television and audio equipment;
  • personal computer and router.

In addition, the power supply provides protection of the connected equipment against voltage fluctuations.

Thanks to the improved power factor corrector operating algorithm, the SW500L works efficiently in conjunction with a generator.

The SW500L UPS with 55 Ah batteries operates on the basis of double-conversion technology, which allows the device to:

  • stabilise the voltage with high accuracy (±2%) over the range (90-295 V) without switching to batteries;
  • instantly and seamlessly switch the load power to the battery when the voltage fails or goes outside the above range;
  • to supply electrical appliances with a voltage with an ideal sinusoidal waveform.

The UPS is equipped with a convection (fanless) cooling system.

Installation and connection

The UPS is mounted on the wall using a special bracket. The battery rack is placed on the floor.

Batteries are installed in the rack strictly in accordance with the operating instructions. It is important that the rack circuit breaker is in the OFF position and its cable is disconnected from the UPS.

The UPS is connected to the mains via a cord with a Schuko plug. The rack with the installed battery is connected to the already switched-on power supply via a TD50A-TD50A cable. The load is connected to the UPS last.

All components for installing and connecting the equipment are included in the scope of delivery.

Battery charging

The batteries in the battery rack are charged by the charger built into the UPS with a current of 5 A.

The power supply features modern technologies for reducing charging time and extending battery life (intelligent charging and battery charge temperature compensation), algorithms for disconnecting the battery at 80-85% discharge (protection against deep discharge), user notifications about battery wear and prediction of autonomy time at the current load.

Protection

The SW500L has electronic protection against:

  • short circuit;
  • sustained output overload;
  • internal overheating.

The UPS is able to automatically restore its operation after the cause of the protective shutdown has been eliminated.

The built-in varistor (2 kV (case-to-wire), 1 kV (wire-to-wire), response time – 50 µs) provides surge protection. High-frequency filters protect the mains from interference in the 150 kHz - 30 MHz range and the load (from phase-to-neutral interference at frequencies up to 2.5 kHz).

In addition, the power supply is equipped with emergency protection against operational faults. When it triggers, the load is de-energised or transferred to the mains via the built-in bypass without interruption.

Control panel

The UPS operation is monitored and its operating parameters configured on the control panel with an LCD display, which includes four control buttons and five LED indicators:

  • "Status" – device operating mode and occurrence of alarms;
  • "Mains" – input mains status;
  • "Bypass" – electronic bypass/ECO mode;
  • "Inverter" – operation from the inverter;
  • "Battery" – battery status.

Types of information on the LCD display:

  • input and output voltage values;
  • UPS load percentage;
  • battery voltage values and their status;
  • active and apparent load power;
  • alarms with indication of their causes.

The UPS control panel is also used to configure various device operating parameters and to start three types of battery test:

  • for 10 seconds (the UPS powers the load from the battery for 10 seconds);
  • for a specified time (the UPS powers the load from the battery for a specified time);
  • to full discharge (the UPS powers the load from the battery until it is fully discharged, measuring the battery capacity and calibrating it).

Tests can be started and configured via the System menu, UPS Command item.

Monitoring tools

A card can be installed in the UPS to monitor the device's operation remotely over a local network or via the internet. Three models of such cards are available with the following interfaces:

  • RS-232;
  • USB or mini-USB;
  • "dry" contacts;
  • Ethernet (protocols: Web/SNMP/NTP/Modbus TCP/SHTYL).

The power supply is monitored via a web browser or the Shtyl Device Manager software. Please note that the expansion board is purchased separately.

All SHTYL manufacturer equipment offers an excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.

  • Advantages

General specifications
Apparent power, kVA 0,5
Active power, kW 0,4
Form factor wall-mounted
Number of phases 1 to 1
Operating modes on-line, autonomous, bypass, ECO
Topology on-line (double conversion)
Country of manufacture Russia
Input characteristics
Generator compatibility yes
Input mains type single-phase three-wire (L, N, PE)
Input power factor 0,99
Limiting input voltage range, V 90-295
Maximum input current, A 3,6
Operating input voltage range, V 175-295 at 100% load, 155-295 at 75% load, 120-295 at 50% load
Power consumption in no-load mode, W 20
Rated input frequency, Hz 50
Rated input voltage, V 220
Soft start yes
Permissible input frequency range, Hz 45-65
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -5, -10, -15, -20, -25 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +5, +10, +15, +20, +25 (default: +20)
Output characteristics
Crest factor 3:1
Maximum output current, A 2,3
Output power factor 0,8
Output voltage type single-phase
Rated output frequency, Hz when operating from the mains – matches the mains frequency; when operating from the battery – set by the user: 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <2.5 with linear load, <4 with non-linear load
Rated AC output voltage, V 220
Output voltage waveform pure sine wave
Efficiency in online mode, % 96
Efficiency in battery mode, % 81
Output voltage stabilisation accuracy, % ±2
Output frequency stabilisation accuracy (when operating from battery), % ±0,2
Overload capacity (when operating in on-line mode or from batteries) 101-105% – no time limit, 105-130% – for 60 s, 130-150% – for 1 s, above 150% – for 0.2 s (followed by switching to bypass)
Efficiency in bypass or ECO mode, % 99
Transfer time to battery mode from ECO mode, ms 7
Overload capacity (when operating via bypass or in ECO mode) 200% for 40 s
Protection
Output overload electronic protection with auto-restart
Overheating electronic protection with auto-restart
Short circuit electronic protection with auto-restart
Protection against UPS failure electronic emergency protection
Protection against deep battery discharge yes
Electronic automatic bypass yes
Surge protection varistor (2 kV (case-to-wire), 1 kV (wire-to-wire), response – 50 µs)
Mains protection against high-frequency interference 150 kHz - 30 MHz
Load protection against mains interference (between phase and neutral) up to 2.5 kHz
Control panel and interfaces
Audible alarm battery mode, low voltage of internal and/or external batteries, battery disconnected/fully discharged/needs replacement, overload and UPS fault
Ethernet option (monitoring card required)
LCD display display of system operating status and main input and output parameters
LED indication status, mains, bypass, inverter, battery
Indication type LCD display and LED indication
"Dry" contacts option (monitoring card required)
mini-USB option (monitoring card required)
RS-232 option (monitoring card required)
Function keys control of the menu displayed on the LCD, UPS configuration
USB option (monitoring card required)
Connection
Input mains power cable with Euro plug
Load (output sockets) EURO F-type with grounding (1 pc.)
UPS connection connector type TD50A
Reliability and performance characteristics
Cooling type convection (fanless)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 80 (non-condensing)
Service life, years at least 10
Warranty period, months 24 (12 per battery)
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Housing colour grey
Weight, kg 56
Overall dimensions HxWxD (unpacked), mm 287x357x112 (without mounting bracket) 287x357x116 (with mounting bracket)
Overall dimensions of the rack HxWxD, mm 602×436×224
Batteries (battery packs)
Battery availability external
Hot-swap of built-in batteries no
Battery runtime (at 80% UPS load) 1 h 45 min
Rated battery voltage, V 24
Battery type sealed, maintenance-free, lead-acid
Battery service life, years 10-12
Battery management functionality residual capacity determination, tests (10-second, for a specified runtime, until full discharge), deep discharge protection, charge temperature compensation
Cold start yes
Rated charge current of the built-in charger, A 5
Capacity of one 12 V battery, Ah 55
External battery capacity, Ah 55
Number of external 12 V batteries, pcs. 2

Write to us

We will reply to info@levrus.ru shortly