The online UPS SW500L with 150 Ah batteries installed in the battery rack BS-24-1W will provide autonomous power supply to devices with a power of up to 500 VA /400 W for 7 h (at 80% load). The battery runtime at other UPS load levels is shown on the Battery runtime tab. Examples of loads include:
- gas boiler and circulation pump;
- water supply and water treatment system;
- video surveillance and alarm system;
- television and audio equipment;
- personal computer, etc.
The UPS also protects equipment from voltage surges and electrical interference.
The SW500L operates efficiently with a generator thanks to an improved power factor corrector algorithm.
The SW500L power supply is based on double conversion technology, which allows:
- stabilise the input voltage with high accuracy (±2%) over the range (90-295 V) without switching to autonomous mode (battery power);
- instantly and seamlessly switch the load power to the battery when the mains voltage fails or its value goes outside the permissible range;
- supply the load with a perfect sinusoidal voltage.
The UPS has a convection (fanless) cooling system.
Installation and connection
The UPS is mounted on the wall using a special bracket. The battery rack is placed on the floor.
Batteries are installed in the rack strictly in accordance with the operating instructions. It is important that the rack circuit breaker is in the OFF position and its cable is disconnected from the UPS.
The UPS is connected to the mains via a cord with a Schuko plug. The rack with the installed battery is connected to the already switched-on power supply via a TD50A-TD50A cable. The load is connected to the UPS last.
All components intended for installing and connecting the devices are included in the scope of delivery.
Battery charging
The batteries in the battery rack are charged by the charger built into the UPS with a current of 5 A.
The power supply features modern technologies for reducing charging time and extending battery life (intelligent charging and battery charge temperature compensation), algorithms for disconnecting the battery at 80-85% discharge (protection against deep discharge), user notifications about battery wear and prediction of autonomy time at the current load.
Protection
The SW500L has electronic protection against:
- short circuit;
- sustained output overload;
- internal overheating.
Automatic restoration of UPS operation is ensured after the cause of the electronic protection tripping is eliminated.
In addition, the UPS has protection against surge voltages and mains interference, as well as emergency protection against malfunctions (when it is triggered, the load is switched off or transferred without interruption to the mains via bypass).
Control panel
The UPS operation is monitored and its operating parameters configured on the control panel with an LCD display, which includes four control buttons and five LED indicators:
- "Status" – device operating mode and occurrence of alarms;
- "Mains" – input mains status;
- "Bypass" – electronic bypass/ECO mode;
- "Inverter" – operation from the inverter;
- "Battery" – battery status.
Types of information on the LCD display:
- input and output voltage values;
- UPS load percentage;
- battery voltage values and their status;
- active and apparent load power;
- alarms with indication of their causes.
The UPS control panel is also used to configure various device operating parameters and to start three types of battery test:
- for 10 seconds (the UPS powers the load from the battery for 10 seconds);
- for a specified time (the UPS powers the load from the battery for a specified time);
- to full discharge (the UPS powers the load from the battery until it is fully discharged, measuring the battery capacity and calibrating it).
Tests can be started and configured via the System menu, UPS Command item.
Monitoring tools
An expansion card can be installed in the UPS to enable local/remote monitoring of its operation. Three models of such cards are available with the following interfaces:
- RS-232;
- USB or mini-USB;
- "dry" contacts;
- Ethernet (protocols: Web/SNMP/NTP/Modbus TCP/SHTYL).
The status of the power supply with an installed board is monitored via a web browser or the Shtyl Device Manager software. The monitoring board is purchased separately.