‎+7 (499) 500-24-60
Moscow, Udaltsova St., 81, bldg 2, office 6
Single-phase UPS

SHTYL SW300SL online UPS (300 VA / 225 W)

  • Brand: Shtil
  • Product Code: SW300SL
  • Availability: Pre-order
22 580 ₽

The online UPS SW300SL ensures uninterrupted operation and protection against mains voltage fluctuations for critical electrical equipment up to 300 VA/225 W, for example:

  • power-dependent boilers;
  • circulation pumps;
  • septic systems with low-power pumps;
  • smart home control units;
  • video surveillance systems;
  • critical low-power household appliances.

The UPS has an advanced power factor corrector algorithm, thanks to which the device interacts excellently with generator sets.

The SW300SL is based on double conversion technology, which allows the device to:

  • continuously correct the voltage over a wide range (90-295 V) and with high accuracy (±2%) without switching to battery mode;
  • instantly transfer consumer power to the battery when the mains fails;
  • to supply the load with a voltage with an ideal sine wave regardless of the operating mode.

The device is completely silent in operation thanks to its convection (fanless) cooling system.

Installation and connection

The SW300SL is mounted on any flat vertical surface that can withstand a load of 6.5 kg. Installation is carried out using self-tapping screws. For convenience, the UPS delivery set includes a special template for marking the surface.

The load is connected to the UPS via a EURO socket located on its enclosure. Connection to the input mains is made using a mains cable with a Euro plug.

Battery operation

For backup power of the load, the SW300SL UPS is equipped with one built-in 12 V battery with a capacity of 9 Ah and a charger (current 1 A). At 100% UPS load, the battery provides autonomous power to consumers for 8 minutes (Battery Runtime Table).

The SW300SL uses modern technologies to reduce charging time and extend battery life (intelligent charging and charge temperature compensation), as well as algorithms for automatically disconnecting the battery at 80-85% discharge (protection against deep discharge), notifying the user of battery wear and predicting the autonomy time at the current load (the value is displayed in the device's web interface; a monitoring card is required for connection).

Control panel

The UPS control panel has function buttons for switching the device on/off, performing a cold start, changing the operating mode (online, bypass or ECO) and testing the battery (10-second forced powering of the load from the battery). The test is started by holding the Mode Change button for 3 seconds.

For monitoring the UPS operation, it has LED indicators:

  • "Status" – device operating mode and occurrence of alarms;
  • "Bypass" – operation via bypass/ECO mode;
  • "Battery" – battery status.

Monitoring and configuration tools

  • RS-232 (Megatec protocol);
  • RS-485 (SHTYL protocol);
  • USB and mini-USB;
  • Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
  • "dry" contacts.

The status of the SW300SL UPS can be monitored in a web browser or in the Shtyl Device Manager (SDM) program. Editing the UPS parameters (start-up and operating mode, output voltage, rated output frequency when operating from the battery, bypass mode, on/off of the audible alarm, battery parameters, battery tests) is performed only via the "Settings" menu of the Shtyl Device Manager program when the computer is locally connected to the UPS via the USB interface or the RS-232 interface.

To remotely view the UPS status in a web browser, the device must be connected to the internet via an Ethernet connector. To set up such a connection, an IC-SNMP/Web or IC-SNMP/mini-USB interface expansion card is required.

Monitoring cards are not included in the standard scope of supply and are purchased separately.

Protection

The SW300SL UPS is equipped with electronic protection against:

  • short circuit;
  • sustained output overload;
  • internal overheating.

The device can restart automatically once the cause of the fault has been eliminated.

The model also has protection against:

  • impulse overvoltages (varistor – 2 kV ("case-wire"), 1 kV ("wire-wire"), response – 50 μs);
  • against high-frequency interference – 150 kHz - 30 MHz;
  • against mains interference (between phase and neutral) – up to 2.5 kHz;
  • operating faults (if they occur, the consumers are either de-energised or seamlessly switched to the mains via the built-in bypass).

The SW300SL model offers the optimal price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.

  • Advantages

General specifications
Apparent power, kVA 0,3
Active power, kW 0,225
Form factor wall-mounted
Number of phases 1 to 1
Operating modes on-line, autonomous, bypass, ECO
Topology on-line (double conversion)
Country of manufacture Russia
Input characteristics
Generator compatibility yes
Input mains type single-phase three-wire (L, N, PE)
Input power factor 0,99
Limiting input voltage range, V 90-295
Maximum input current, A 1,7
Operating input voltage range, V 175-295 at 100% load, 155-295 at 75% load, 120-295 at 50% load
Power consumption in no-load mode, W 16
Rated input frequency, Hz 50
Rated input voltage, V 230
Soft start yes
Permissible input frequency range, Hz 45-65
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -5, -10, -15, -20, -25 (default: -15)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +5, +10, +15, +20, +25 (default: +10)
Maximum bypass current, A 4,5
Output characteristics
Crest factor 3:1
Maximum output current, A 1,2
Output power factor 0,75
Output voltage type single-phase
Rated output frequency, Hz when operating from the mains – matches the mains frequency; when operating from the battery – set by the user: 50 (default)/ 60 (monitoring card required)
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <2.5 with linear load, <4 with non-linear load
Rated AC output voltage, V 230
Output voltage waveform pure sine wave
Efficiency in online mode, % 91
Efficiency in battery mode, % 82
Output voltage stabilisation accuracy, % ±2
Output frequency stabilisation accuracy (when operating from battery), % ±0,2
Overload capacity (when operating in on-line mode or from batteries) 101-105% – for 3 min, 105-130% – for 60 s, 130-150% – for 1 s, above 150% – for 0.2 s
Efficiency in bypass or ECO mode, % 99
Transfer time to battery mode from ECO mode, ms 7
Overload capacity (when operating via bypass or in ECO mode) 200% for 40 s
Protection
Output overload electronic protection with auto-restart
Overheating electronic protection with auto-restart
Short circuit electronic protection with auto-restart
Protection against UPS failure electronic emergency protection
Protection against deep battery discharge yes
Electronic automatic bypass yes
Surge protection varistor (2 kV (case-to-wire), 1 kV (wire-to-wire), response – 50 µs)
Mains protection against high-frequency interference 150 kHz - 30 MHz
Load protection against mains interference (between phase and neutral) up to 2.5 kHz
Control panel and interfaces
Audible alarm battery mode (every 4 s), low battery voltage (every 2 s), battery disconnected/fully discharged/needs replacement (every 0,5 s), overload and UPS fault (continuous)
Ethernet option (monitoring card required)
LED indication status, bypass, battery
RS-485 option (monitoring card required, data exchange only with SHTYL equipment)
Indication type LED indication
"Dry" contacts option (monitoring card required)
mini-USB option (monitoring card required)
RS-232 option (monitoring card required)
Function keys "On", "Off", "Mode change"
USB option (monitoring card required)
Temperature sensor option (monitoring card required)
Connection
Input mains power cable with Euro plug
Load (output sockets) EURO F-type with grounding (1 pc.)
Reliability and performance characteristics
Cooling type convection (fanless)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 80 (non-condensing)
Service life, years 10
Warranty period, months 24
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Housing colour grey
Weight, kg 6,5
Overall dimensions HxWxD (unpacked), mm 283x285x93
Overall dimensions HxWxD (packed), mm 330x330x140
Batteries (battery packs)
Battery availability built-in
Hot-swap of built-in batteries no
Battery runtime (at 80% UPS load) 12 min
Battery runtime at 100% (50%) UPS load, min 8 (23)
Internal battery capacity, Ah 9
Number of built-in 12 V batteries, pcs. 1
Rated battery voltage, V 12
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 7 (depending on operating conditions)
Battery management functionality deep discharge protection (LVD), charge temperature compensation, 10-second battery test
Cold start yes
Rated charge current of the built-in charger, A 1
Built-in battery charge time, h no more than 8 (up to 90% capacity)

Write to us