The online UPS SW300L with an external 55 Ah battery housed in the floor-standing battery rack BS-12-1W provides backup power to a critical load with an output power of 300 VA/225 W for 1 h 50 min (at 80% load). The battery runtime at other UPS load levels is shown on the Battery runtime tab. The solution is used for a gas boiler and circulation pump, water purification system, CCTV camera, TV or router.
In addition to uninterruptible power supply, the UPS protects the connected equipment against voltage fluctuations and electrical interference.
The power supply operates excellently in conjunction with a generator thanks to an improved power factor corrector algorithm.
The SW300L UPS is based on double-conversion technology, thanks to which the device is capable of:
- stabilise the input voltage over a wide range (90-295 V) and with high accuracy (±2%) without switching to battery;
- instantly and seamlessly switch the load power to the battery when the mains voltage fails or its value goes outside the above range;
- supply the load with a perfect sinusoidal voltage.
The power supply is equipped with a convection (silent) cooling system.
Installation and connection
The SW300L is mounted on any flat vertical surface that can withstand a load of 4 kg. Installation is carried out using self-tapping screws. The battery rack is placed on the floor.
Batteries are installed in the rack strictly in accordance with the operating instructions. It is important that the rack circuit breaker is in the OFF position and its cable is disconnected from the UPS.
The UPS is connected to the mains via a cord with a Schuko plug. The rack with the installed battery is connected to the already switched-on power supply via a TD50A-TD50A cable. The load is connected to the UPS last.
All components intended for installing and connecting the devices are included in the scope of delivery.
Control panel
The operation of the power supply is monitored using the LED indicators located on the front panel:
- "Status" – occurrence of alarms;
- "Bypass" – operation via the bypass circuit/ECO mode;
- "Battery" – battery status.
Assessing the status of all three indicators allows the operating mode of the device to be determined.
The 'Mode change' key allows selection of the UPS operating mode: online, bypass or ECO. It is also used (when held for 3 seconds) to run a battery test – 10 seconds of forced battery-powered load supply.
Battery charging
Charging of the connected 55 Ah battery is performed by the charger built into the UPS with a current of 6 A.
The SW300L uses modern technologies to reduce charging time and extend battery life (intelligent charging and battery charge temperature compensation), as well as algorithms that allow the battery to be disconnected at 80-85% discharge (protection against deep discharge), notify the user of battery wear and predict the autonomy time at the current load (the value is displayed in the device's web interface; a monitoring card is required for connection).
Protection
The SW300L has electronic protection against:
- short circuit;
- sustained output overload;
- internal overheating.
The device resumes operation automatically after the cause of the electronic protection tripping is eliminated.
In addition, the UPS provides protection against:
- impulse overvoltages (varistor – 2 kV ("case-wire"), 1 kV ("wire-wire"), response – 50 μs);
- operating faults (when the emergency protection trips, the consumers are disconnected or seamlessly switched to the mains via the built-in bypass).
High-frequency filters protect the mains from interference in the 150 kHz - 30 MHz range and the load (from phase-to-neutral interference up to 2.5 kHz).
The battery rack BS-12-1W has a built-in 2P C32 circuit breaker for battery protection.
Monitoring tools
A monitoring card can be installed in the SW300L to monitor its status and configure its parameters. The UPS supports several compatible monitoring cards with the following interfaces:
- RS-232 (Megatec protocol);
- RS-485 (SHTYL protocol);
- USB and mini-USB;
- Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
- "dry" contacts;
- temperature sensor.
With the card installed, the UPS status can be monitored in a web browser or in the Shtyl Device Manager (SDM) software. The power supply parameters (for example, setting its output voltage) are edited only using the Shtyl Device Manager software when the computer is locally connected to the UPS via the USB interface or the RS-232 interface.
The boards are not included in the standard scope of supply and are purchased separately.
The SW300L UPS kit offers an excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.
- Advantages