The SW1000L online UPS with 75 Ah batteries installed in the BS-36-1W battery rack will provide backup power to a load with a capacity of up to 1000 VA / 900 W for 2 h (at 80% load). The autonomous operation time at other UPS load levels is presented on the Autonomous operation tab. Examples of equipment include:
- heating and water supply systems;
- pumping equipment;
- water supply and water treatment systems;
- security and fire suppression systems.
In addition, the power supply protects the connected load from voltage fluctuations and electrical interference.
The SW1000L is capable of operating in conjunction with a generator thanks to the improved operating algorithm of the power factor corrector.
The SW1000L UPS with 75 Ah batteries uses double conversion technology, which achieves:
- voltage stabilisation with high accuracy (±2%) over a wide range (90-295 V) without switching to battery operation;
- instant and seamless transition of the load power to the battery when the mains voltage fails or its value goes outside the operating range;
- supplying the load with a voltage with an ideal sinusoidal waveform.
The UPS is equipped with a low-noise cooling system based on a fan with an adaptive speed mode.
Installation and connection
The SW1000L is mounted on the wall using a special bracket. The battery rack is installed on the floor.
Installation of the battery in the rack is carried out in accordance with the operating instructions. It is important that the rack circuit breaker is in the OFF position and its cable is disconnected from the UPS.
The UPS is connected to the mains via a cord with a Schuko plug. The rack with the installed battery is connected to the already switched-on power supply via a TD50A-TD50A cable. The load is connected to the UPS last.
All components used in the installation and connection of the power supply are included in the scope of delivery.
Battery charging
The batteries in the battery rack are charged by the charger built into the UPS with a current of 5 A.
The power supply features modern technologies for reducing charging time and extending battery life (intelligent charging and battery charge temperature compensation), algorithms for disconnecting the battery at 80-85% discharge (protection against deep discharge), user notifications about battery wear and prediction of autonomy time at the current load.
Protection
The SW1000L has electronic protection against:
- short circuit;
- sustained output overload;
- internal overheating.
Once the cause of the electronic protection tripping is eliminated, the UPS can automatically restore its operation.
In addition, the device is equipped with protection against surge voltages and mains interference, as well as emergency protection against operational faults (when the protection is activated, the device de-energises the load or switches it to the mains via bypass without interruption).
Control panel
The UPS operation is monitored and its operating parameters configured on the control panel with an LCD display, which includes four control buttons and five LED indicators:
- "Status" – device operating mode and occurrence of alarms;
- "Mains" – input mains status;
- "Bypass" – electronic bypass/ECO mode;
- "Inverter" – operation from the inverter;
- "Battery" – battery status.
Types of information on the LCD display:
- input and output voltage values;
- UPS load percentage;
- battery voltage values and their status;
- active and apparent load power;
- alarms with indication of their causes.
The UPS control panel is also used to configure various device operating parameters and to start three types of battery test:
- for 10 seconds (the UPS powers the load from the battery for 10 seconds);
- for a specified time (the UPS powers the load from the battery for a specified time);
- to full discharge (the UPS powers the load from the battery until it is fully discharged, measuring the battery capacity and calibrating it).
Tests can be started and configured via the System menu, UPS Command item.
Monitoring tools
The UPS rear panel has a slot for installing a board that enables local/remote monitoring of the device. Three models of such boards with the following interfaces are available:
- RS-232;
- USB or mini-USB;
- "dry" contacts;
- Ethernet (protocols: Web/SNMP/NTP/Modbus TCP/SHTYL).
After installing the board, UPS monitoring and control can be performed in two ways: via a web browser or the Shtyl Device Manager (SDM) software. The monitoring board is not included in the scope of supply and must be ordered separately.
The high-precision equipment from the manufacturer SHTYL is characterised by an excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.
- Advantages