SHTYL SW1000L UPS kit (1000 VA/900 W) with battery for 35 min

  • Brand: Shtil
  • Product Code: SW1000L-27Ah
  • Availability: Pre-order
67 720 ₽

The online UPS SW1000L with battery module BM-36-27, containing 9 batteries with a total capacity of 27 Ah, provides backup power to a load of 1000 VA /900 W for 35 min (at 80% load). The battery runtime at other UPS load levels is shown on the Battery runtime tab. Examples of equipment include:

  • gas boiler and circulation pump;
  • water supply and water treatment system;
  • video surveillance system;
  • audio and video equipment;
  • personal computer;
  • low-power household appliances.

In addition to backup power supply, the UPS protects equipment against voltage fluctuations and electrical interference.

The SW1000L functions excellently in conjunction with a generator thanks to the improved operating algorithm of the power factor corrector.

The SW1000L UPS with the BM-36-27 battery module is based on double-conversion technology, which provides:

  • voltage correction with high accuracy (±2%) over the range 90-295 V and without switching to battery;
  • instant and seamless transition of the load power to the battery when the power fails or the voltage goes outside the stabilisation range;
  • power supply to the load with an ideal sine wave voltage.

The UPS is cooled by a low-noise fan with adaptive speed.

Installation and connection

The UPS and the BM-36-27 battery module are wall-mounted using special brackets.

For connection to the UPS, the battery module has a TD50A "Anderson" connector. The load is connected to the UPS last.

All components intended for installing and connecting the devices are included in the scope of delivery.

Battery charging

The batteries of the battery module are charged by the charger built into the UPS with a current of 5 A.

The power supply features modern technologies for reducing charging time and extending battery life (intelligent charging and battery charge temperature compensation), algorithms for disconnecting the battery at 80-85% discharge (protection against deep discharge), user notifications about battery wear and prediction of autonomy time at the current load.

Protection

The SW1000L is provided with electronic protection against:

  • short circuit;
  • sustained output overload;
  • internal overheating.

The device automatically resumes operation once the cause of the protective shutdown has been eliminated.

In addition, the UPS provides protection against surge voltages and mains interference, as well as emergency protection against faults (when they occur, the load is de-energised or transferred without interruption to mains power via the built-in bypass).

Control panel

Monitoring of operation and configuration of the UPS operating parameters is performed on a control panel with an LCD display, which includes four control buttons and five LED indicators:

  • "Status" – device operating mode and occurrence of alarms;
  • "Mains" – input mains status;
  • "Bypass" – electronic bypass/ECO mode;
  • "Inverter" – operation from the inverter;
  • "Battery" – battery status.

Types of information on the LCD display:

  • input and output voltage values;
  • UPS load percentage;
  • battery voltage values and their status;
  • active and apparent load power;
  • alarms with indication of their causes.

The UPS control panel is also used to configure various device operating parameters and to start three types of battery test:

  • for 10 seconds (the UPS powers the load from the battery for 10 seconds);
  • for a specified time (the UPS powers the load from the battery for a specified time);
  • to full discharge (the UPS powers the load from the battery until it is fully discharged, measuring the battery capacity and calibrating it).

Tests can be started and configured via the System menu, UPS Command item.

Monitoring tools

The UPS can provide local/remote monitoring of operation by installing an expansion card. Three models of such cards with the following interfaces are available:

  • RS-232;
  • USB or mini-USB;
  • "dry" contacts;
  • Ethernet (protocols: Web/SNMP/NTP/Modbus TCP/SHTYL).

The UPS with an installed board can be monitored in two ways: via a web browser or the dedicated Shtyl Device Manager software.

The board is not included in the UPS scope of supply and is purchased separately.

SHTYL equipment offers an excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.

  • Advantages

General specifications
Apparent power, kVA 1
Active power, kW 0,9
Form factor wall-mounted
Number of phases 1 to 1
Operating modes on-line, autonomous, bypass, ECO
Topology on-line (double conversion)
Country of manufacture Russia
Input characteristics
Generator compatibility yes
Input mains type single-phase three-wire (L, N, PE)
Input power factor 0,99
Limiting input voltage range, V 90-295
Maximum input current, A 7,2
Operating input voltage range, V 175-295 at 100% load, 155-295 at 75% load, 120-295 at 50% load
Power consumption in no-load mode, W 25
Rated input frequency, Hz 50
Rated input voltage, V 220
Soft start yes
Permissible input frequency range, Hz 45-65
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -5, -10, -15, -20, -25 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +5, +10, +15, +20, +25 (default: +20)
Output characteristics
Crest factor 3:1
Maximum output current, A 4,5
Output power factor 0,9
Output voltage type single-phase
Rated output frequency, Hz when operating from the mains – matches the mains frequency; when operating from the battery – set by the user: 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <2.5 with linear load, <4 with non-linear load
Rated AC output voltage, V 220
Output voltage waveform pure sine wave
Efficiency in online mode, % 96
Efficiency in battery mode, % 86
Output voltage stabilisation accuracy, % ±2
Output frequency stabilisation accuracy (when operating from battery), % ±0,2
Overload capacity (when operating in on-line mode or from batteries) 101-105% – no time limit, 105-130% – for 60 s, 130-150% – for 1 s, above 150% – for 0.2 s (followed by switching to bypass)
Efficiency in bypass or ECO mode, % 99
Transfer time to battery mode from ECO mode, ms 7
Overload capacity (when operating via bypass or in ECO mode) 200% for 40 s
Protection
Output overload electronic protection with auto-restart
Overheating electronic protection with auto-restart
Short circuit electronic protection with auto-restart
Protection against UPS failure electronic emergency protection
Protection against deep battery discharge yes
Electronic automatic bypass yes
Surge protection varistor (2 kV (case-to-wire), 1 kV (wire-to-wire), response – 50 µs)
Mains protection against high-frequency interference 150 kHz - 30 MHz
Load protection against mains interference (between phase and neutral) up to 2.5 kHz
Control panel and interfaces
Audible alarm battery mode, low voltage of internal and/or external batteries, battery disconnected/fully discharged/needs replacement, overload and UPS fault
Ethernet option (monitoring card required)
LCD display display of system operating status and main input and output parameters
LED indication status, mains, bypass, inverter, battery
Indication type LCD display and LED indication
"Dry" contacts option (monitoring card required)
mini-USB option (monitoring card required)
RS-232 option (monitoring card required)
Function keys control of the menu displayed on the LCD, UPS configuration
USB option (monitoring card required)
Connection
Input mains power cable with Euro plug
Load (output sockets) EURO F-type with grounding (2 pcs.)
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 80 (non-condensing)
Service life, years at least 10
Warranty period, months 24 (12 per battery module)
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Housing colour grey
Weight, kg 34
Overall dimensions HxWxD (unpacked), mm 379x357x112 (without mounting bracket) 379x357x116 (with mounting bracket)
Overall dimensions of the battery module HxWxD, mm 386x357x116
Batteries (battery packs)
Battery availability external
Hot-swap of built-in batteries no
Battery runtime (at 80% UPS load) 35 min
Rated battery voltage, V 36
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 7 (depending on operating conditions)
Battery management functionality residual capacity determination, tests (10-second, for a specified runtime, until full discharge), deep discharge protection, charge temperature compensation
Cold start yes
Rated charge current of the built-in charger, A 5
Capacity of one 12 V battery, Ah 9
Number of external 12 V batteries, pcs. 9
Total battery capacity in the module, Ah 27