SHTYL SW1000L UPS kit (1000 VA/900 W) with battery for 20 min

  • Brand: Shtil
  • Product Code: SW1000L-18Ah
  • Availability: Pre-order
58 440 ₽

The SW1000L online UPS with the BM-36-18 battery module, in which 6 batteries with a total capacity of 18 Ah are installed, will provide backup power for 20 min (at 80% load) to electrical equipment with a capacity of 1000 VA / 900 W. The autonomous operation time at other UPS load levels is presented on the Autonomous operation tab. Examples of loads are:

  • gas boilers and other heating equipment;
  • water supply and water treatment systems;
  • security alarm and video surveillance systems;
  • computer and multimedia equipment;
  • low-power household appliances.

The UPS will also protect equipment from voltage surges and electrical interference. Thanks to the improved power factor corrector operating algorithm, the power supply interacts fully with generators.

The operation of the SW1000L UPS is based on double energy conversion technology, which allows the device to:

  • correct the voltage with high accuracy (±2%) over the range (90-295 V) without switching to battery;
  • instantly transfer the load power supply to the battery when the power fails or the voltage goes outside the operating range;
  • to supply the load with a voltage of ideal sinusoidal waveform.

The power supply is cooled by a low-noise fan with adaptive speed control.

Installation and connection

The SW1000L UPS and the BM-36-18 battery module are mounted on a flat vertical surface using special brackets.

For connection to the UPS, the battery module has a TD50A "Anderson" connector. The load is connected to the UPS last.

All components intended for installing and connecting the devices are included in the scope of delivery.

Battery charging

The batteries of the battery module are charged by the charger built into the UPS with a current of 5 A.

The UPS employs modern technologies to reduce charging time and extend battery service life (intelligent charging and battery charge temperature compensation), algorithms for disconnecting the battery at 80-85% discharge (protection against deep discharge), notifying the user of battery wear and predicting autonomy time at the current load.

Protection

The SW1000L is equipped with electronic protection against:

  • short circuit;
  • sustained output overload;
  • internal overheating.

The UPS supports automatic restart after the cause of the protection trip has been eliminated.

In addition, the device features:

  • with surge and mains interference protection;
  • emergency protection against operational faults (when they occur, the load is de-energised or switched to mains operation without interruption via the bypass).

Control panel

Configuration and monitoring of the main operating parameters of the product are performed using the control and indication panel. It includes an LCD display, four control buttons and five LED indicators:

  • "Status" – device operating mode and occurrence of alarms;
  • "Mains" – input mains status;
  • "Bypass" – electronic bypass/ECO mode;
  • "Inverter" – operation from the inverter;
  • "Battery" – battery status.

Types of information on the LCD display:

  • input and output voltage values;
  • UPS load percentage;
  • battery voltage values and their status;
  • active and apparent load power;
  • alarms with indication of their causes.

In addition, using the display and function keys on the control panel, the user can configure various device operating parameters and run three types of battery test:

  • 10-second (the UPS supplies the load from the battery for 10 seconds);
  • for a specified time (the UPS powers the load from the battery for a specified time);
  • to full discharge (the UPS powers the load from the battery until it is fully discharged, measuring the battery capacity and calibrating it).

Tests can be started and configured via the System menu, UPS Command item.

Monitoring tools

The SW1000L allows the installation of an expansion card for local/remote monitoring of the device's operation. Three models of such cards are available with the following interfaces:

  • RS-232;
  • USB or mini-USB;
  • "dry" contacts;
  • Ethernet (protocols: Web/SNMP/NTP/Modbus TCP/SHTYL).

UPS monitoring with the installed board is possible via a web browser or the Shtyl Device Manager software. The board is an optional accessory and is not included in the standard scope of supply of the device.

SHTYL power supply systems are characterised by an excellent price/quality combination compared with similar products from foreign vendors on the Russian power supply systems market.

  • Advantages

General specifications
Apparent power, kVA 1
Active power, kW 0,9
Form factor wall-mounted
Number of phases 1 to 1
Operating modes on-line, autonomous, bypass, ECO
Topology on-line (double conversion)
Country of manufacture Russia
Input characteristics
Generator compatibility yes
Input mains type single-phase three-wire (L, N, PE)
Input power factor 0,99
Limiting input voltage range, V 90-295
Maximum input current, A 7,2
Operating input voltage range, V 175-295 at 100% load, 155-295 at 75% load, 120-295 at 50% load
Power consumption in no-load mode, W 25
Rated input frequency, Hz 50
Rated input voltage, V 220
Soft start yes
Permissible input frequency range, Hz 45-65
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -5, -10, -15, -20, -25 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +5, +10, +15, +20, +25 (default: +20)
Output characteristics
Crest factor 3:1
Maximum output current, A 4,5
Output power factor 0,9
Output voltage type single-phase
Rated output frequency, Hz when operating from the mains – matches the mains frequency; when operating from the battery – set by the user: 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <2.5 with linear load, <4 with non-linear load
Rated AC output voltage, V 220
Output voltage waveform pure sine wave
Efficiency in online mode, % 96
Efficiency in battery mode, % 86
Output voltage stabilisation accuracy, % ±2
Output frequency stabilisation accuracy (when operating from battery), % ±0,2
Overload capacity (when operating in on-line mode or from batteries) 101-105% – no time limit, 105-130% – for 60 s, 130-150% – for 1 s, above 150% – for 0.2 s (followed by switching to bypass)
Efficiency in bypass or ECO mode, % 99
Transfer time to battery mode from ECO mode, ms 7
Overload capacity (when operating via bypass or in ECO mode) 200% for 40 s
Protection
Output overload electronic protection with auto-restart
Overheating electronic protection with auto-restart
Short circuit electronic protection with auto-restart
Protection against UPS failure electronic emergency protection
Protection against deep battery discharge yes
Electronic automatic bypass yes
Surge protection varistor (2 kV, 1/50 µs)
Mains protection against high-frequency interference 150 kHz - 30 MHz
Load protection against mains interference (between phase and neutral) up to 2.5 kHz
Control panel and interfaces
Audible alarm battery mode, low voltage of internal and/or external batteries, battery disconnected/fully discharged/needs replacement, overload and UPS fault
Ethernet option (monitoring card required)
LCD display display of system operating status and main input and output parameters
LED indication status, mains, bypass, inverter, battery
Indication type LCD display and LED indication
"Dry" contacts option (monitoring card required)
mini-USB option (monitoring card required)
RS-232 option (monitoring card required)
Function keys control of the menu displayed on the LCD, UPS configuration
USB option (monitoring card required)
Connection
Input mains power cable with Euro plug
Load (output sockets) EURO F-type with grounding (2 pcs.)
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 80 (non-condensing)
Service life, years at least 10
Warranty period, months 24 (12 per battery module)
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Housing colour grey
Weight, kg 26
Overall dimensions HxWxD (unpacked), mm 379x357x112 (without mounting bracket) 379x357x116 (with mounting bracket)
Overall dimensions of the battery module HxWxD, mm 386x357x116
Batteries (battery packs)
Battery availability external
Hot-swap of built-in batteries no
Battery runtime (at 80% UPS load) 20 min
Rated battery voltage, V 36
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 7 (depending on operating conditions)
Battery management functionality residual capacity determination, tests (10-second, for a specified runtime, until full discharge), deep discharge protection, charge temperature compensation
Cold start yes
Rated charge current of the built-in charger, A 5
Capacity of one 12 V battery, Ah 9
Number of external 12 V batteries, pcs. 6
Total battery capacity in the module, Ah 18