The STR300SL-27 online UPS in floor/rack design is used to provide autonomous operation and protection against voltage fluctuations for critical equipment with a total capacity of up to 300 VA/225 W, for example:
- network equipment;
- video surveillance systems;
- emergency signalling;
- smart home control units;
- low-power household appliances.
The UPS has an advanced power factor corrector algorithm, which ensures efficient interaction with generator sets.
The STR300L-27 UPS uses double conversion technology, providing:
- continuous voltage stabilisation in the 90-295 V range with high accuracy (±2%) without switching to the batteries;
- instant and seamless switching of the load power to batteries when the mains power fails or goes outside the stabilisation range;
- power supply to consumers with an ideal sine wave voltage in any operating mode.
The device is equipped with a low-noise fan with automatic speed control.
Installation and connection
The universal cabinet STR300L-27 allows installation in two ways:
- floor-standing in a vertical position;
- horizontally in a 19-inch rack (if the device is not placed on a shelf, it is recommended to additionally purchase a rack-mounting kit).
The device is connected via the following connectors:
- for the load – three "computer" C13 sockets;
- for the mains – cable with a Schuko plug, 1.5 m long.
Control panel
The STR300SL-27 control panel has function buttons and three LED indicators:
- "Status" – device operating mode and occurrence of alarms;
- "Bypass" – operation via bypass/ECO mode;
- "Battery" – battery status.
The function buttons allow you to switch the UPS on/off, perform a cold start, change the operating mode (online, bypass or ECO), and test the batteries (10 seconds of forced battery-powered load supply). The test is started by holding the Mode Change button for 3 seconds.
Attention! Battery testing is recommended at least once every six months.
Battery operation
Battery operation of the load is provided by the built-in charger (current 3 A) and a battery block with three batteries with a total capacity of 27 Ah. At 100% load, the backup power supply to the connected electrical equipment will last 32 minutes (Battery runtime table).
Attention! The internal battery block is initially not connected to the UPS. This is done to prevent self-discharge of its battery. Before the first start-up of the device, the connector in the battery compartment must be connected. For more details, see the operation manual.
To increase the autonomous runtime to 1 h 20 min at 100% load, connection of the BMRT-12-27 battery module is provided (Battery Runtime Table).
The UPS uses modern technologies to reduce charging time and extend battery life (intelligent charging and charge temperature compensation), as well as algorithms that allow:
- disconnect the battery at 80-85% discharge (protection against deep discharge);
- notify the user of battery wear;
- predict the autonomy time at the current load (the value is displayed in the device web interface; a monitoring card is required for connection).
Monitoring and configuration tools
- RS-232 (Megatec protocol);
- RS-485 (SHTYL protocol);
- USB and mini-USB;
- Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
- "dry" contacts;
- temperature sensor.
The status of the STR300SL-27 UPS can be monitored in a web browser or in the Shtyl Device Manager (SDM) program. Editing the UPS parameters (start-up and operating mode, output voltage, rated output frequency when operating from the battery, bypass mode, on/off of the audible alarm, battery parameters, battery tests) is performed only via the "Settings" menu of the Shtyl Device Manager program when the computer is locally connected to the UPS via the USB interface or the RS-232 interface.
To remotely view the UPS status in a web browser, the device must be connected to the internet via an Ethernet connector. To set up such a connection, an IC-SNMP/Web or IC-SNMP/mini-USB interface expansion card is required.
Please note! The monitoring card is not included in the scope of supply and must be purchased separately.
Protection
The STR300SL-27 is equipped with several types of electronic protection:
- against overload;
- against short circuit;
- against internal overheating.
Once the cause of the protection tripping is eliminated, the device automatically restarts.
In addition, the UPS has:
- mains protection against high-frequency interference – 150 kHz - 30 MHz;
- load protection against mains interference (between phase and neutral) – up to 2.5 kHz;
- emergency protection against operational faults (when they occur, the UPS switches off the load or transfers its power supply to the mains without interruption via the bypass).
The STR300SL-27 online UPS from the SHTYL brand offers an excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.
- Advantages