The STR1110SL online UPS in floor/rack (rack/tower) design is intended to provide backup power and protection against unstable voltage for equipment with a total power consumption of up to 10 kVA / 8 kW. Examples of loads include:
- server and network devices;
- computer equipment;
- APCS;
- security and video surveillance systems;
- public address and emergency lighting systems.
The advanced power factor corrector algorithm enables the UPS to operate correctly with diesel/petrol generators.
STR1110SL with double conversion technology is capable of protecting against all types of power supply interruptions. Thanks to this operating principle, the device performs:
- signal adjustment over a wide range (90-310 V) to autonomous mode;
- instantaneous and seamless mode switching – transfer of power to the mains/batteries;
- power supply to the load with voltage accuracy of ±2% and an ideal sine wave.
Installation and connection
The UPS has a universal (rack/tower) form factor. It can be installed on the floor or in 19-inch rails of racks and cabinets. When placing in a rack without shelves, it is recommended to purchase a mounting kit to support the product along its entire depth.
To connect the load, the STR1110SL rear panel provides several connectors: eight C13 sockets, two C19 sockets and terminals (L, N). The input mains is connected via terminal outputs (L, N, PE). A cable with a conductor cross-section of 10 mm2 is used for connection.
Battery operation
The UPS has two built-in battery blocks with batteries of a total capacity of 9 Ah and a 4 A charger. At 70% UPS load, consumers will be provided with autonomous power for 2 minutes. To increase the backup power time, external batteries can be connected to the UPS. The autonomous operation time from the built-in batteries at various load levels of the power supply is presented on the Autonomous operation tab.
In the event of failure of the built-in battery blocks, hot-swap replacement is provided, which will not affect the warranty.
Attention! Initially, the battery blocks are not connected to the UPS. This is done to prevent their self-discharge. Therefore, before the first switching on, it is necessary to install the battery blocks in the device housing, connecting the corresponding connectors. Read more about this in the operating manual.
The STR1110SL uses modern technologies to reduce charging time and extend battery service life (intelligent charging and battery charge temperature compensation), as well as algorithms that allow the batteries to be disconnected at 80-85% discharge (protection against «deep» discharge), notify the user of battery wear and predict the autonomy time at the current load.
Control panel
The UPS is equipped with a modern LCD display with a gyroscope that automatically changes its orientation depending on the position of the device's enclosure.
Information on the LCD display:
- input voltage and input frequency values;
- output voltage and output frequency values;
- UPS load percentage relative to the rated output power;
- active and apparent power;
- mimic diagram showing the UPS status;
- battery temperature, voltage and current;
- internal temperature of the device;
- battery charge level and predicted autonomy time;
- alarm notification indicating the cause;
- operating modes: online, bypass or battery power;
- audible alarm status.
Configuring the main UPS operating parameters:
- operating mode (on-line or ECO);
- bypass mode (auto, on or off);
- start method (auto or by button);
- output voltage (220-240 V, in 5 V steps);
- nominal output frequency when operating from the battery(50/60 Hz);
- the battery charge level at which the non-priority load is switched off (from 10 to 90% in 5% steps);
- the deep discharge level of the batteries.
Starting three types of battery test:
- 10-second (load supply for 10 seconds);
- for a specified time (powering the load for a specified time);
- to full discharge (powering the load until the battery is fully discharged, measuring the residual capacity).
Battery tests are started and configured via the Commands menu, Battery Tests item.
Cooling system
The cooling system consists of two low-noise fans whose speed depends on the load level.
Protection
The STR1110SL UPS uses electronic protection against:
- overload;
- short circuit;
- internal overheating.
Once the cause of the electronic protection activation is eliminated, the device restarts.
In addition, the UPS provides protection against high-frequency mains interference and surge voltages, as well as emergency protection against faults (if faults occur, the load is de-energised or switched without interruption to the mains via the bypass).
Monitoring tools
For remote monitoring of STR1110SL operation, its rear panel provides two slots for installing interface expansion cards:
- RS-232 (Megatec protocol);
- RS-485 (Modbus RTU/SHTYL protocols);
- USB and mini-USB;
- Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
- "dry" contacts.