The STR1106SL online UPS in floor/rack (rack/tower) design is intended to provide backup power and protection against unstable voltage for equipment with a total power consumption of up to 6000 VA / 5400 W, for example:
- servers and data centre equipment;
- telecommunications apparatus;
- automated control systems;
- security and video surveillance systems.
Thanks to the improved power factor corrector operating algorithm, the device functions correctly in conjunction with diesel/petrol generators.
STR1106SL is an online UPS operating on the basis of double energy conversion technology. Thanks to this, the device is capable of:
- correct the input voltage over a wide range (90-310 V) without switching to battery mode;
- instantly and seamlessly transfer appliance power to batteries when the mains fails or the input voltage goes outside the stabilisation range;
- continuously supply the load with voltage at an accurate value (±2% of nominal) and with a perfect sine wave.
Installation and connection
The UPS form factor is universal (rack/tower). This allows the unit to be installed both in 19-inch rack or cabinet rails and on the floor. If installed in a rack without shelves, it is recommended to purchase a mounting kit to support the product along its full depth.
The rear panel of the STR1106SL has load connection sockets: eight C13 sockets, two C19 sockets and terminal outputs (L, N). The input mains is connected via a terminal block (L, N, PE). A cable with a conductor cross-section of 10 mm2 is used for connection.
Battery operation
The UPS has two built-in battery blocks with batteries of a total capacity of 9 Ah and a 4 A charger. At 100% UPS load, consumers will be provided with autonomous power for 3 minutes. To increase the backup time, external batteries can be connected to the UPS. The battery runtime from internal batteries at various power supply load levels is shown on the Battery Runtime tab.
In the event of failure of the built-in battery blocks, hot-swap replacement is provided, which will not affect the warranty.
Attention! Initially, the battery blocks are not connected to the UPS. This is done to prevent their self-discharge. Therefore, before the first switching on, it is necessary to install the battery blocks in the device housing, connecting the corresponding connectors. Read more about this in the operating manual.
The STR1106SL uses modern technologies to reduce charging time and extend battery service life (intelligent charging and battery charge temperature compensation), as well as algorithms that allow the batteries to be disconnected at 80-85% discharge (protection against «deep» discharge), notify the user of battery wear and predict the autonomy time at the current load.
Control panel
The UPS is equipped with a modern LCD display with a gyroscope that automatically changes its orientation depending on the position of the device's enclosure.
Information on the LCD display:
- input voltage and input frequency values;
- output voltage and output frequency values;
- UPS load percentage relative to the rated output power;
- active and apparent power;
- mimic diagram showing the UPS status;
- battery temperature, voltage and current;
- internal temperature of the device;
- battery charge level and predicted autonomy time;
- alarm notification indicating the cause;
- operating modes: online, bypass or battery power;
- audible alarm status.
Configuring the main UPS operating parameters:
- operating mode (on-line or ECO);
- bypass mode (auto, on or off);
- start method (auto or by button);
- output voltage (220-240 V, in 5 V steps);
- nominal output frequency when operating from the battery (50/60 Hz);
- the battery charge level at which the non-priority load is switched off (from 10 to 90% in 5% steps);
- the deep discharge level of the batteries.
Starting three types of battery test:
- 10-second (load supply for 10 seconds);
- for a specified time (powering the load for a specified time);
- to full discharge (powering the load until full discharge, measuring the residual capacity).
Battery tests are started and configured via the Commands menu, Battery Tests item.
Cooling system
The cooling system consists of two low-noise fans whose speed depends on the load level.
Protection
The STR1106SL UPS uses electronic protection against:
- overload;
- short circuit;
- internal overheating.
Once the cause of the electronic protection activation is eliminated, the device restarts.
In addition, the UPS provides protection against high-frequency mains interference and surge voltages, as well as emergency protection against faults (if faults occur, the load is de-energised or switched without interruption to the mains via the bypass).
Monitoring tools
For remote monitoring of STR1106SL operation, its rear panel provides two slots for installing interface expansion cards:
- RS-232 (Megatec protocol);
- RS-485 (Modbus RTU/SHTYL protocols);
- USB and mini-USB;
- Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
- "dry" contacts.
The status of the UPS and the load connected to it is monitored in a web browser or via the Shtyl Device Manager (SDM) software. The boards are not included in the basic scope of supply and are purchased additionally.
- Advantages