Single-phase UPS

SHTYL STR1101LD online UPS (1000 VA / 900 W)

  • Brand: Shtil
  • Product Code: STR1101LD
  • Availability: Pre-order
44 550 ₽

The STR1101LD online UPS in universal design is intended to provide uninterrupted, high-quality power to a wide range of devices with a total capacity of up to 1000 VA / 900 W, for example:

  • server rooms, computer rooms and data centres;
  • network equipment and telecommunications hardware;
  • security, alarm and video surveillance systems;
  • instrumentation and process control system devices.

Thanks to the improved power factor corrector operating algorithm, the STR1101LD model functions excellently in conjunction with diesel generator sets.

STR1101LD is a UPS with double conversion technology, thanks to which the device enables:

  • stabilise the input voltage over a wide range (90-295 V) and with high accuracy (±2%) without switching to battery;
  • instantly and seamlessly switch the load power to the battery when the mains voltage fails;
  • supply the load with a perfect sinusoidal voltage.

Installation and connection

STR1101LD can be installed in two ways: vertically on any flat horizontal surface (on the feet for vertical installation), horizontally in the 19-inch rails of telecommunications cabinets or racks. Mounting parts for both methods are included in the device's scope of supply.

To connect electrical equipment, the UPS has the following connectors: six "computer" C13 sockets and one Euro socket. Connection to the input mains is made via the C14 connector.

Attention! The load connection sockets are segmented into primary and non-priority. When the UPS operates from the battery, a drop in the battery charge level to 20% (this value can be changed in the menu settings) will de-energise the non-priority sockets. The primary output sockets remain powered right up to a 'deep' battery discharge.

Battery operation

The UPS has a built-in charger (10 A current) and the ability to connect external lead-acid batteries, which provide the required load runtime (Battery Runtime Table).

Depending on the required battery runtime, external batteries can be installed both in battery modules and in battery racks.

The UPS employs special technologies aimed at reducing charging time and extending battery service life:

  • intelligent battery charging algorithm (charging is first performed in cyclic mode (elevated voltage), then in float mode (standby voltage));
  • battery charge temperature compensation (automatic adjustment of charge voltage depending on battery temperature).

In addition, the UPS features special algorithms that allow the battery to be disconnected at 80-85% discharge (protection against deep discharge), notify the user in advance of battery wear, and accurately predict the autonomy time at the current load.

Control panel

STR1101LD has a modern digital LCD display with a built-in gyroscope, thanks to which the UPS automatically changes the screen orientation depending on the position of the device.

Information on the LCD display:

  • input voltage and input frequency values;
  • output voltage and output frequency values;
  • UPS load percentage relative to the rated output power;
  • active and apparent power;
  • mimic diagram showing the UPS status;
  • battery temperature, voltage and current;
  • internal temperature of the device;
  • battery charge level and predicted autonomy time;
  • alarm notification indicating the cause;
  • operating modes: online, bypass or battery power;
  • audible alarm status.

Configuring the main UPS operating parameters:

  • operating mode (on-line or ECO);
  • bypass mode (auto, on or off);
  • start method (auto or by button);
  • output voltage (220, 230 or 240 V);
  • nominal output frequency (50/60 Hz);
  • the battery charge level at which the non-priority load is switched off (from 10 to 90% in 5% steps);
  • the deep discharge level of the batteries.

Starting three types of battery test:

  • 10-second (the UPS supplies the load from the battery for 10 seconds);
  • for a specified time (the UPS powers the load from the battery for a specified time);
  • to full discharge (the UPS powers the load from the battery until it is fully discharged, measuring the residual capacity).

Battery tests are started and configured via the Commands menu, Battery Tests item.

Cooling system

The device is equipped with a low-noise fan with automatic speed control.

Protection

The STR1101LD UPS uses electronic protection against:

  • overload;
  • short circuit;
  • internal overheating.

Once the cause of this protection activation is eliminated, the device restarts.

In addition, the UPS has protection against high-frequency mains interference and surge voltages, as well as emergency protection against operational faults (when activated, the load is disconnected or transferred to the mains via bypass without interruption).

Monitoring tools

STR1101LD offers extensive capabilities for organising local/remote monitoring and control of operation. For this purpose, expansion cards with the following interfaces are connected to the UPS:

  • RS-232 (Megatec protocol);
  • RS-485 (Modbus RTU/SHTYL protocols);
  • USB and mini-USB;
  • Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
  • "dry" contacts.

The operation of the UPS with an installed card can be monitored directly in a web browser or in the Shtyl Device Manager (SDM) software. Please note that the cards are not included in the standard scope of supply and are purchased separately.

Excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.

  • Advantages

General specifications
Apparent power, kVA 1
Active power, kW 0,9
Form factor floor-standing/rack-mount
Number of phases 1 to 1
Operating modes on-line, autonomous, bypass, ECO
Topology on-line (double conversion)
Country of manufacture Russia
Input characteristics
Generator compatibility yes
Input mains type single-phase three-wire (L, N, PE)
Input power factor 0,99
Limiting input voltage range, V 90-295
Maximum input current, A 9
Operating input voltage range, V 175-295 at 100% load, 155-295 at 75% load, 120-295 at 50% load
Power consumption in no-load mode, W 25
Rated input frequency, Hz 50
Rated input voltage, V 220
Soft start yes
Permissible input frequency range, Hz 45-65
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -5, -10, -15, -20, -25 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +5, +10, +15, +20, +25 (default: +20)
Output characteristics
Crest factor 3:1
Maximum output current, A 4,5
Output power factor 0,9
Output voltage type single-phase
Rated output frequency, Hz when operating from the mains – matches the mains frequency; when operating from the battery – set by the user: 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <2.5 with linear load, <4 with non-linear load
Rated AC output voltage, V 220
Output voltage waveform pure sine wave
Efficiency in online mode, % 95
Efficiency in battery mode, % 86
Output voltage stabilisation accuracy, % ±2
Output frequency stabilisation accuracy (when operating from battery), % ±0,2
Overload capacity (when operating in on-line mode or from batteries) 101-105% – no time limit, 105-130% – for 60 s, 130-150% – for 1 s, above 150% – for 0.2 s (followed by switching to bypass)
Efficiency in bypass or ECO mode, % 99
Transfer time to battery mode from ECO mode, ms 7
Overload capacity (when operating via bypass or in ECO mode) 200% for 40 s
Protection
Output overload electronic protection with auto-restart
Overheating electronic protection with auto-restart
Short circuit electronic protection with auto-restart
Protection against UPS failure electronic emergency protection
Protection against deep battery discharge yes
Electronic automatic bypass yes
Surge protection varistor (2 kV (case-to-wire), 1 kV (wire-to-wire), response – 50 µs)
Mains protection against high-frequency interference 150 kHz - 30 MHz
Load protection against mains interference (between phase and neutral) up to 2.5 kHz
Control panel and interfaces
Audible alarm battery mode (every 4 s), low battery voltage (every 2 s), battery disconnected/fully discharged/needs replacement (every 0,5 s), overload and UPS fault (continuous)
Ethernet option (monitoring card required)
RS-485 option (monitoring card required)
Indication type LCD display
EPO pluggable screw terminal block, wire cross-section: 0.08-1.2 mm².
"Dry" contacts option (monitoring card required)
mini-USB option (monitoring card required)
RS-232 option (monitoring card required)
Function keys switching between screens displayed on the LCD, UPS configuration
USB option (monitoring card required)
Rotating LCD display with built-in gyroscope display of system operating status and main input and output parameters
Connection
Input mains IEC-320-C14
Load (output sockets) IEC-320-C13 (6 pcs.), Euro socket (1 pc.)
Priority disconnection of non-priority load yes
The charge level at which the non-priority load is disconnected user-settable (default – 20%)
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 80 (non-condensing)
Service life, years at least 10
Warranty period, months 24
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Housing colour black
Weight, kg 8
Rack mounting height, U 2
Overall dimensions HxWxD (unpacked), mm 88(2U)x482x401(rack-mount) 466x207x401 (floor-standing)
Overall dimensions HxWxD (packed), mm 138x480x512
Batteries (battery packs)
Battery availability external (option)
Hot-swap of built-in batteries yes
Battery runtime (at 80% UPS load) Depends on the external battery capacity
Rated battery voltage, V 36
Battery type sealed, maintenance-free, lead-acid
Battery management functionality residual capacity determination, tests (10-second, for a specified runtime, until full discharge), deep discharge protection, charge temperature compensation
Cold start yes
Rated charge current of the built-in charger, A 10