The kit consists of an STR1101L online UPS with a capacity of 1 kVA / 0,9 kW and two BMRT-36-18 battery modules with a total total battery capacity of 36 Ah. The solution is suitable for uninterruptible power supply and protection against voltage fluctuations for a server, computer, network equipment and video surveillance system.
Thanks to the improved power factor corrector operating algorithm, the UPS functions excellently in conjunction with diesel generator sets.
UPS with double conversion technology, by means of which the following is performed:
- voltage correction over the range 90-295 V without switching to battery;
- instant switching to autonomous mode when the power fails;
- continuous power supply to equipment with voltage accuracy of ±2% and a pure sine wave.
Installation and connection
The UPS and the battery module are installed vertically on the floor/shelving or horizontally in the 19-inch rails of telecommunications cabinets or racks. Mounting parts for both methods are included.
To connect electrical equipment, the UPS has the following connectors: six "computer" C13 sockets and one Euro socket. Connection to the input mains is made via the C14 connector.
Attention! The load connection sockets are segmented into primary and non-priority. When the UPS operates from the battery, a drop in the battery charge level to 20% (this value can be changed in the menu settings) will de-energise the non-priority sockets. The primary output sockets remain powered right up to a 'deep' battery discharge.
Battery operation
The UPS is equipped with a built-in charger with a current of 5 A. Backup power for the connected equipment is provided by two 18 Ah battery modules, each containing two battery blocks BP-36-09/RT. Each block contains three 12 V batteries of 9 Ah each. Parallel connection of battery modules is supported (up to 4 pcs.).
At 80% UPS load, consumers will be provided with autonomous power for 45 minutes. The battery runtime at other load levels is shown on the Battery runtime tab.
In the event of failure of the built-in batteries, hot-swap replacement is provided. Battery replacement does not affect the warranty.
Attention! The internal battery blocks in the module are initially disconnected. This is done to prevent their self-discharge. Therefore, before the first start-up of the device, the connector in the battery compartment must be connected. For more details, see the operation manual.
The UPS employs modern technologies to reduce charging time and extend battery service life (intelligent charging and battery charge temperature compensation), as well as algorithms that allow the battery to be disconnected at 80-85% discharge (protection against deep discharge), notify the user of battery wear and predict autonomy time.
Control panel
The UPS features an LCD display with a built-in gyroscope, which automatically changes the screen orientation depending on the device position.
Information on the LCD display:
- input/output voltage and input/output frequency values;
- UPS load percentage relative to the rated output power;
- active and apparent power;
- mimic diagram showing the UPS status;
- battery temperature, voltage and current;
- internal temperature of the device;
- battery charge level and predicted autonomy time;
- alarm notification indicating the cause;
- operating modes: online, bypass or battery power;
- audible alarm status.
Configuring the main UPS operating parameters:
- operating mode (on-line or ECO) and bypass (auto, on or off);
- start method (auto or by button);
- output voltage (220, 230 or 240 V);
- nominal output frequency (50/60 Hz);
- the battery charge level at which the non-priority load is switched off (from 10 to 90% in 5% steps);
- the deep discharge level of the batteries.
Starting three types of battery test:
- 10-second (the UPS supplies the load from the battery for 10 seconds);
- for a specified time (the UPS powers the load from the battery for a specified time);
- to full discharge (the UPS powers the load from the battery until it is fully discharged, measuring the residual capacity).
Protection
The UPS features modern electronic protection against overload, short circuit and internal overheating. Automatic restart of the UPS is supported after the cause of the protection trip has been eliminated.
The device is provided with mains protection against high-frequency interference (150 kHz - 30 MHz), load protection against mains interference (between phase and neutral, up to 2.5 kHz) and emergency protection against operational faults.
Cooling system
The device is equipped with a low-noise fan with automatic speed control.
Monitoring tools
The UPS provides local/remote status monitoring. The function is implemented using cards, which can have different interfaces: RS-232 (Megatec protocol), RS-485 (Modbus RTU / SHTYL protocols), USB, mini-USB, Ethernet (Web / SNMP / NTP / Modbus TCP / SHTYL protocols) and dry contacts. The cards are not included in the standard scope of supply and are purchased separately.
The operation of the UPS with an installed card can be monitored directly in a web browser or in the Shtyl Device Manager (SDM) software.
The kit with the STR1101L UPS offers an excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.
- Advantages