‎+7 (499) 500-24-60
Moscow, Udaltsova St., 81, bldg 2, office 6
Single-phase UPS

SHTYL ST1106L UPS kit (6 kVA / 5.4 kW) with battery for 7 min

  • Brand: Shtil
  • Product Code: ST1106L-9Ah
  • Availability: Pre-order
196 640 ₽

The kit consisting of the ST1106L online UPS and the BMT-192-09 battery module is designed to provide uninterrupted operation and reliable protection against voltage fluctuations for a single-phase load of domestic or commercial use with a total capacity of 6 kVA /5.4 kW. This may include heating boilers, circulation pumps, multimedia systems, video equipment, server equipment, security and video surveillance systems.

Thanks to the improved power factor corrector operating algorithm, the UPS functions excellently in conjunction with diesel generator sets.

The included UPS with high-frequency double energy conversion, thanks to which the device:

  • stabilises the voltage over a wide range (90-310 V) without switching to battery;
  • instantly and seamlessly switches to the battery when the mains fails;
  • supplies the load with an ideal sinusoidal voltage with a stabilisation accuracy of ±2%.

Installation and connection

The UPS and the battery module are in a floor-standing (tower) design. They can be installed on any flat horizontal surface. Terminal blocks located in a closed compartment on the rear panel of the device are used to connect the load and provide power.

Battery operation

ST1106L has a built-in charger (current from 1 to 4 A, setting step – 0.5 A). The battery module powers the load autonomously for 7 minutes at 80% UPS load (Autonomy Time Table).

The UPS employs modern technologies to reduce charging time and extend battery service life (intelligent charging and battery charge temperature compensation).

The UPS has special algorithms that allow:

  • disconnect the battery at 80-85% discharge (protection against deep discharge);
  • notify the user in advance of battery wear;
  • accurately predict the autonomy time at the current load.

Control panel

The main operating parameters of the UPS are monitored and configured using the control panel. It includes an LCD display, four function keys and five LED indicators:

  • "Status" – indicates the device operating mode;
  • "Mains" – indicates mains status;
  • "Bypass" – indicates a switch to bypass/ECO mode;
  • "Inverter" – indicates inverter operation;
  • "Battery" – shows the battery status.

Information on the LCD display:

  • input and output voltage values;
  • UPS load percentage;
  • battery voltage values and their status;
  • active and apparent load power;
  • alarms with indication of their causes.

The control panel allows three battery tests to be performed: for 10 seconds, for a specified time and until full discharge.

Protection

The UPS has built-in electronic protection against output overload, short circuit and internal overheating. The UPS also has built-in protection against mains interference and surge voltages, as well as emergency fault protection (when activated, the load is de-energised or switched to the mains via bypass).

Excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.

Monitoring tools

ST1106L has functionality that allows local/remote operation monitoring. The rear panel of the device provides two slots for installing monitoring cards with the following interfaces:

  • RS-232 (Megatec protocol) and RS-485 (Modbus RTU/SHTYL protocols);
  • USB and mini-USB;
  • Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
  • "dry" contacts.

The operation of the power supply with an installed board can be monitored and tracked via a web browser or the dedicated Shtyl Device Manager (SDM) software. The expansion boards are not included in the scope of supply and are purchased separately.

  • Advantages

General specifications
Apparent power, kVA 6
Active power, kW 5,4
Form factor floor-standing
Number of phases 1 to 1
Operating modes on-line, autonomous, bypass, ECO
Topology on-line (double conversion)
Country of manufacture Russia
Input characteristics
Generator compatibility yes
Input mains type single-phase three-wire (L, N, PE)
Input power factor 0,99
Limiting input voltage range, V 90-310
Maximum input current, A 38
Operating input voltage range, V 165-310 at 100% load, 135-310 at 80% load, 90-310 at 60% load
Rated input frequency, Hz 50
Rated input voltage, V 220
Soft start yes
Permissible input frequency range, Hz 43-57
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -5, -10, -15, -20, -25 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +5, +10, +15, +20, +25 (default: +20)
Output characteristics
Crest factor 3:1
Maximum output current, A 27
Output power factor 0,9
Output voltage type single-phase
Rated output frequency, Hz when operating from the mains – matches the mains frequency; when operating from the battery – set by the user: 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <2 with linear load, <4 with non-linear load
Rated AC output voltage, V 220
Output voltage waveform pure sine wave
Efficiency in online mode, % 95
Efficiency in battery mode, % 94
Output voltage stabilisation accuracy, % ±2
Output frequency stabilisation accuracy (when operating from battery), % ±0,1
Overload capacity (when operating in on-line mode or from batteries) less than 105% – unlimited, 105-150% – at least 5 s, more than 150% – no more than 5 s (followed by switching to bypass)
Efficiency in bypass or ECO mode, % 99
Transfer time to battery mode from ECO mode, ms 5
Protection
Output overload electronic protection with auto-restart
Overheating electronic protection with auto-restart
Short circuit electronic protection with auto-restart
Protection against UPS failure electronic emergency protection
Protection against deep battery discharge yes
Electronic automatic bypass yes
Surge protection varistor (2 kV (case-to-wire), 1 kV (wire-to-wire), response – 50 µs)
Mains protection against high-frequency interference 150 kHz - 30 MHz
Load protection against mains interference (between phase and neutral) up to 2.5 kHz
Control panel and interfaces
Audible alarm battery mode, low voltage of internal and/or external batteries, battery disconnected/fully discharged/needs replacement, overload and UPS fault
Ethernet option (monitoring card required)
LCD display display of system operating status and main input and output parameters
LED indication status, mains, bypass, inverter, battery
RS-485 option (monitoring card required)
Indication type LCD display and LED indication
EPO pluggable screw terminal block, wire cross-section: 0.08-1.2 mm².
"Dry" contacts option (monitoring card required)
mini-USB option (monitoring card required)
RS-232 option (monitoring card required)
Function keys control of the menu displayed on the LCD, UPS configuration
USB option (monitoring card required)
Connection
Input mains terminal connection (L, N, PE)
Load (output sockets) terminal connection (L, N, PE)
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 80 (non-condensing)
Service life, years at least 10
Warranty period, months 24
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Housing colour grey
Weight, kg UPS – 18 Battery module – 58
Overall dimensions HxWxD (unpacked), mm UPS – 438x250x572Battery module – 440x250x591
Overall dimensions HxWxD (packed), mm UPS – 615x300x485
Batteries (battery packs)
Battery availability external
Hot-swap of built-in batteries no
Battery runtime (at 80% UPS load) 7 min
Battery runtime at 100% (50%) UPS load, min 5 (12)
Rated battery voltage, V 192
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 7 (depending on operating conditions)
Battery management functionality residual capacity determination, tests (10-second, for a specified runtime, until full discharge), deep discharge protection, charge temperature compensation
Cold start yes
Rated charge current of the built-in charger, A from 1 to 4 (setting step – 0.5 A)

Write to us

We will reply to info@levrus.ru shortly