The kit consists of an ST1103TL online UPS and a BMT-96-09 battery module and is used to ensure uninterrupted operation of standalone electrical appliances or a group of devices with a capacity of up to 3 kVA/ 2.7 kW in the event of periodic power outages. The device also reliably protects connected equipment from unstable mains voltage, for example, heating equipment, household appliances and commercial equipment.
Thanks to the improved power factor corrector operating algorithm, the UPS functions excellently in conjunction with diesel generator sets.
An online UPS with double voltage conversion, thanks to which the device enables:
- stabilise the voltage over the range (90-295 V) without switching to battery;
- instantly switch the power to the battery when the mains fails;
- supply the load with voltage with high accuracy (±2%) and a pure sine wave.
Installation and connection
The UPS and the battery module are in a floor-standing design – they are installed on any flat horizontal surface. To power the load, the rear panel of the UPS has: two Schuko sockets, three C13 "computer" sockets and terminal blocks. The UPS is connected to the mains via terminal connections.
Battery operation
To provide autonomous operation of the load, the ST1103TL has a charger (current 4 A). The battery module provides backup power for devices for 8 minutes at 80% UPS load (Battery runtime table).
The UPS employs modern technologies to reduce charging time and extend battery service life (intelligent charging and battery charge temperature compensation).
The model features special algorithms that allow:
- disconnect the battery at 80-85% discharge (protection against deep discharge);
- notify the user in advance of battery wear;
- accurately predict the autonomy time at the current load.
Control panel
The main operating parameters of the product are monitored and configured using the control panel. It includes an LCD display, four function keys and five LED indicators:
- "Status" – indicates the device operating mode;
- "Mains" – indicates mains status;
- "Bypass" – indicates a switch to bypass/ECO mode;
- "Inverter" – indicates inverter operation;
- "Battery" – shows the battery status.
The LCD display shows the following information:
- input and output voltage values;
- UPS load percentage;
- battery voltage values and their status;
- active and apparent load power;
- alarms with indication of their causes.
The control panel allows three battery tests to be performed: for 10 seconds, for a specified time or until full discharge.
Protection
The UPS is equipped with electronic protection against: short circuit, prolonged output overload and internal overheating. After the cause of the protection trip is eliminated, the UPS automatically resumes operation.
The UPS has a built-in varistor to protect the load from overvoltages, mains interference filters and emergency fault protection.
Excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.
Monitoring tools
ST1103TL supports local/remote operation monitoring by installing expansion cards with the following interfaces:
- RS-232 (Megatec protocol);
- RS-485 (Modbus RTU/SHTYL protocols);
- USB and mini-USB;
- Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
- "dry" contacts.
The UPS with an installed board is monitored in a web browser or the Shtyl Device Manager (SDM) software. Please note that the expansion boards are not included in the standard scope of supply and are purchased separately.
- Advantages