Single-phase UPS

SHTYL ST1103TL UPS kit (3 kVA / 2.7 kW) with battery for 17 minutes

  • Brand: Shtil
  • Product Code: ST1103TL-18Ah
  • Availability: Pre-order
122 290 ₽

The kit consists of an ST1103TL online UPS and a BMT-96-18 battery module and is used to provide uninterruptible operation of stand-alone electrical appliances or a group of devices with a capacity of up to 3 kVA/ 2,7 kW in the event of periodic power outages. The device also reliably protects connected equipment from unstable mains voltage, for example heating equipment, household appliances and commercial equipment.

Thanks to the improved power factor corrector operating algorithm, the UPS functions excellently in conjunction with diesel generator sets.

An online UPS with double voltage conversion, thanks to which the device enables:

  • stabilise the voltage over the range (90-295 V) without switching to battery;
  • instantly switch the power to the battery when the mains fails;
  • supply the load with voltage with high accuracy (±2%) and a pure sine wave.

Installation and connection

The UPS and the battery module are in a floor-standing design – they are installed on any flat horizontal surface. To power the load, the rear panel of the UPS has: two Schuko sockets, three C13 "computer" sockets and terminal blocks. The UPS is connected to the mains via terminal connections.

Battery operation

To provide autonomous operation of the load, the ST1103TL has a charger (current 4 A). The battery module provides backup power for devices for 17 minutes at 80% UPS load (Battery runtime table).

The UPS employs modern technologies to reduce charging time and extend battery service life (intelligent charging and battery charge temperature compensation).

The model features special algorithms that allow:

  • disconnect the battery at 80-85% discharge (protection against deep discharge);
  • notify the user in advance of battery wear;
  • accurately predict the autonomy time at the current load.

Control panel

The main operating parameters of the product are monitored and configured using the control panel. It includes an LCD display, four function keys and five LED indicators:

  • "Status" – indicates the device operating mode;
  • "Mains" – indicates mains status;
  • "Bypass" – indicates a switch to bypass/ECO mode;
  • "Inverter" – indicates inverter operation;
  • "Battery" – shows the battery status.

The LCD display shows the following information:

  • input and output voltage values;
  • UPS load percentage;
  • battery voltage values and their status;
  • active and apparent load power;
  • alarms with indication of their causes.

The control panel allows three battery tests to be performed: for 10 seconds, for a specified time or until full discharge.

Protection

The UPS is equipped with electronic protection against: short circuit, prolonged output overload and internal overheating. After the cause of the protection trip is eliminated, the UPS automatically resumes operation.

The UPS has a built-in varistor to protect the load from overvoltages, mains interference filters and emergency fault protection.

Excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.

Monitoring tools

ST1103TL supports local/remote operation monitoring by installing expansion cards with the following interfaces:

  • RS-232 (Megatec protocol);
  • RS-485 (Modbus RTU/SHTYL protocols);
  • USB and mini-USB;
  • Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
  • "dry" contacts.

The UPS with an installed board is monitored in a web browser or the Shtyl Device Manager (SDM) software. Please note that the expansion boards are not included in the standard scope of supply and are purchased separately.

  • Advantages

General specifications
Apparent power, kVA 3
Active power, kW 2,7
Form factor floor-standing
Number of phases 1 to 1
Operating modes on-line, autonomous, bypass, ECO
Topology on-line (double conversion)
Country of manufacture Russia
Input characteristics
Generator compatibility yes
Input mains type single-phase three-wire (L, N, PE)
Input power factor 0,99
Limiting input voltage range, V 90-295
Maximum input current, A 21
Operating input voltage range, V 175-295 at 100% load, 155-295 at 75% load, 120-295 at 50% load
Power consumption in no-load mode, W 40
Rated input frequency, Hz 50
Rated input voltage, V 220
Soft start yes
Permissible input frequency range, Hz 45-65
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -5, -10, -15, -20, -25 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +5, +10, +15, +20, +25 (default: +20)
Output characteristics
Crest factor 3:1
Maximum output current, A 13
Output power factor 0,9
Output voltage type single-phase
Rated output frequency, Hz when operating from the mains – matches the mains frequency; when operating from the battery – set by the user: 50/60 (default – 50)
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <2.5 with linear load, <4 with non-linear load
Rated AC output voltage, V 220
Output voltage waveform pure sine wave
Efficiency in online mode, % 95
Efficiency in battery mode, % 86
Output voltage stabilisation accuracy, % ±2
Output frequency stabilisation accuracy (when operating from battery), % ±0,2
Overload capacity (when operating in on-line mode or from batteries) 101-105% – no time limit, 105-130% – for 60 s, 130-150% – for 1 s, above 150% – for 0.2 s (followed by switching to bypass)
Efficiency in bypass or ECO mode, % 99
Transfer time to battery mode from ECO mode, ms 7
Overload capacity (when operating via bypass or in ECO mode) 200% for 40 s
Protection
Output overload electronic protection with auto-restart
Overheating electronic protection with auto-restart
Short circuit electronic protection with auto-restart
Protection against UPS failure electronic emergency protection
Protection against deep battery discharge yes
Electronic automatic bypass yes
Surge protection varistor (2 kV (case-to-wire), 1 kV (wire-to-wire), response – 50 µs)
Mains protection against high-frequency interference 150 kHz - 30 MHz
Load protection against mains interference (between phase and neutral) up to 2.5 kHz
Control panel and interfaces
Audible alarm battery mode (every 4 s), low battery voltage (every 2 s), battery disconnected/fully discharged/needs replacement (every 0,5 s), overload and UPS fault (continuous)
Ethernet option (monitoring card required)
LCD display display of system operating status and main input and output parameters
LED indication status, mains, bypass, inverter, batteries
RS-485 option (monitoring card required)
Indication type LCD display and LED indication
EPO two-contact screw terminal (terminal block), conductor cross-section: 0.08-1.2 mm².
"Dry" contacts option (monitoring card required)
mini-USB option (monitoring card required)
RS-232 option (monitoring card required)
Function keys control of the menu displayed on the LCD, UPS configuration
USB option (monitoring card required)
Connection
Input mains terminal connection (L, N, PE)
Load (output sockets) IEC-320-C13 (3 pcs.), EURO F-type with earthing (2 pcs.), terminals
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 80 (non-condensing)
Service life, years at least 10
Warranty period, months 24
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Housing colour grey
Weight, kg UPS – 14Battery module – 58
Overall dimensions HxWxD (unpacked), mm UPS – 346x210x443Battery module – 346x210x442
Overall dimensions HxWxD (packed), mm UPS – 505x260x395Battery module – 395x260x505
Batteries (battery packs)
Battery availability external
Hot-swap of built-in batteries no
Battery runtime (at 80% UPS load) 17 min
Battery runtime at 100% (50%) UPS load, min 33 (10)
Rated battery voltage, V 96
Battery type sealed, maintenance-free, lead-acid
Battery management functionality residual capacity determination, tests (10-second, for a specified runtime, until full discharge), deep discharge protection, charge temperature compensation
Cold start yes
Rated charge current of the built-in charger, A 4