SHTYL SR3110L online UPS (10 kVA / 8 kW)

  • Brand: Shtil
  • Product Code: SR3110L
  • Availability: Pre-order
164 200 ₽

The SR3110L online UPS with three-phase input and single-phase output is designed to provide uninterruptible power supply and protection against voltage fluctuations in a 380 V network for critical single-phase appliances with a total capacity of up to 10 kVA /8 kW, for example:

  • server rooms, computer rooms and data centres;
  • IT infrastructure of small and medium-sized businesses;
  • network and telecommunications equipment;
  • security, intruder and alarm systems;
  • process control system equipment.

Thanks to the 3-in-1 configuration, the UPS allows a single-phase load to be connected to a three-phase mains with even loading of all supply phases (the power of the connected devices may exceed the power of an individual phase), which eliminates the possibility of mains imbalance and removes the need for constant phase-to-phase balancing.

The SR3110L is a UPS with high-frequency double conversion of energy, thanks to which the device allows:

  • stabilise the input voltage over a wide range (phase voltage – 90-295 V) without switching to autonomous mode;
  • instantly and seamlessly switch the load power to the battery when the mains voltage fails;
  • supply the load with a perfect sinusoidal voltage with high stabilisation accuracy (±2%).

Thanks to the improved power factor corrector operating algorithm, the SR3110L model functions excellently in conjunction with diesel generator sets.

Installation and connection

The UPS has a rack-mount design, which allows the device to be placed in 19-inch rails of telecommunications cabinets and racks.

The terminal blocks on the rear panel of the enclosure provide convenient connection of the load and the input mains.

Battery operation

For autonomous operation of the load, the UPS has a built-in charger (current from 1 to 4, setting step 0.5 A) and a connector for connecting external batteries. The maximum capacity of external batteries is 100 Ah (without an external charger) and 360 Ah (with an external charger), which provides autonomous operation for 50 min or 5 h respectively (at 100% load) (Battery Runtime Table).

Batteries are installed in dedicated battery modules or telecommunications cabinets.

The SR3110L uses modern technologies to reduce charging time and extend battery service life (intelligent charging and battery charge temperature compensation).

In addition, the model features special algorithms that allow:

  • disconnect the battery at 80-85% discharge (protection against deep discharge);
  • notify the user in advance of battery wear;
  • accurately predict the autonomy time at the current load.

Control panel

The main operating parameters of the UPS are monitored and configured using the control panel. It includes an LCD display, four function keys and five LED indicators:

  • "Fault" – a fault has occurred in the device operation;
  • "Mains" – input mains normal, UPS in normal (online) operation;
  • "Bypass" – a switch to bypass has been performed;
  • "Output" – voltage is supplied to the load;
  • "Battery" – battery status.

Information on the LCD display:

  • input and output voltage values;
  • UPS load percentage;
  • input mains and output frequency;
  • battery voltage values;
  • active and apparent load power;
  • output status;
  • alarms with indication of causes.

The control panel allows three battery tests to be performed:

  • 10-second (the UPS supplies the load from the battery for 10 seconds);
  • for a specified time (the UPS powers the load from the battery for a specified time);
  • to full discharge (the UPS powers the load from the battery until it is fully discharged, measuring the residual capacity).

Tests are started via the System menu, UPS Command item.

Protection

Model SR3110L features electronic protection against:

  • short circuit;
  • output overload;
  • internal overheating.

Once the cause of the protection tripping is eliminated, the device automatically restarts.

In addition, the UPS is equipped with protection against high-frequency mains interference and surge voltages, as well as emergency protection against operational faults (when activated, the load is disconnected or transferred to the mains via bypass without interruption).

Using a separate input for the automatic electronic bypass prevents load imbalance on one of the supply phases when operating in bypass mode.

Monitoring tools

Model SR3110L supports local/remote operation monitoring. On the rear panel of the device there are two slots for installing expansion boards with the following interfaces:

  • RS-232 (Megatec protocol);
  • RS-485 (Modbus RTU/SHTYL protocols);
  • USB and mini-USB;
  • Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
  • "dry" contacts.

UPS operation with an installed card can be monitored in a web browser or via the dedicated Shtyl Device Manager software.

Please note that expansion boards are not included in the standard scope of supply and must be purchased separately.

Excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.

  • Advantages

General specifications
Apparent power, kVA 10
Active power, kW 8
Form factor rack-mount
Number of phases 3-in-1
Operating modes on-line, autonomous, bypass, ECO
Topology on-line (double conversion)
Country of manufacture Russia
Input characteristics
Generator compatibility yes
Input mains type three-phase five-wire with common neutral (L1, L2, L3, N, PE)
Input power factor 0,99
Maximum input current per phase, A 20
Rated input frequency, Hz 50
Soft start yes
Permissible input frequency range, Hz 43-57
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -5, -10, -15, -20, -25 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +5, +10, +15, +20, +25 (default: +20)
Limiting phase/line input voltage range, V 90-295/155-510
Operating phase/line input voltage range, V 175-295 at 100% load, 155-295 at 75% load, 120-295 at 50% load
Rated phase-to-neutral/phase-to-phase input voltage, V 220/380
Output characteristics
Crest factor 3:1
Maximum output current, A 45
Output power factor 0,8
Output voltage type single-phase
Rated output frequency, Hz when operating from the mains – matches the mains frequency; when operating from the battery – set by the user: 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <2 with linear load, <4 with non-linear load
Rated AC output voltage, V 220
Output voltage waveform pure sine wave
Efficiency in online mode, % 95
Efficiency in battery mode, % 94
Output voltage stabilisation accuracy, % ±2
Output frequency stabilisation accuracy (when operating from battery), % ±0,1
Overload capacity (when operating in on-line mode or from batteries) less than 105% – unlimited, 105-150% – at least 5 s, more than 150% – no more than 5 s (followed by switching to bypass)
Efficiency in bypass or ECO mode, % 99
Transfer time to battery mode from ECO mode, ms 5
Protection
Output overload electronic protection with auto-restart
Overheating electronic protection with auto-restart
Short circuit electronic protection with auto-restart
Protection against UPS failure electronic emergency protection
Protection against deep battery discharge yes
Electronic automatic bypass yes
Surge protection varistor (2 kV (case-to-wire), 1 kV (wire-to-wire), response – 50 µs)
Mains protection against high-frequency interference 150 kHz - 30 MHz
Control panel and interfaces
Audible alarm battery mode, low voltage of internal and/or external batteries, battery disconnected/fully discharged/needs replacement, overload and UPS fault
Ethernet option (monitoring card required)
LCD display display of system operating status and main input and output parameters
LED indication status, mains, bypass, inverter, battery
RS-485 option (monitoring card required)
Indication type LCD display and LED indication
EPO pluggable screw terminal block, wire cross-section: 0.08-1.2 mm².
"Dry" contacts option (monitoring card required)
mini-USB option (monitoring card required)
RS-232 option (monitoring card required)
Function keys control of the menu displayed on the LCD, UPS configuration
USB option (monitoring card required)
Separate electronic bypass input yes
Connection
Input mains terminal connection (L1, L2, L3, N, PE)
Load (output sockets) terminal connection (L, N, PE)
Bypass input terminal connection (L, N, PE)
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 95 (non-condensing)
Service life, years at least 10
Warranty period, months 24
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Housing colour grey
Weight, kg 16
Rack mounting height, U 3
Overall dimensions HxWxD (unpacked), mm 133x483x530
Overall dimensions HxWxD (packed), mm 175x490x612
Batteries (battery packs)
Battery availability external (option)
Battery runtime (at 80% UPS load) Depends on the external battery capacity
Rated battery voltage, V 192
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 7 (depending on operating conditions)
Battery management functionality residual capacity determination, tests (10-second, for a specified runtime, until full discharge), deep discharge protection, charge temperature compensation
Cold start yes
Rated charge current of the built-in charger, A from 1 to 4 (setting step – 0.5 A)