‎+7 (499) 500-24-60
Moscow, Udaltsova St., 81, bldg 2, office 6
Single-phase UPS

SHTYL SR1103L UPS kit (3 kVA / 2.7 kW) with battery for 3 h

  • Brand: Shtil
  • Product Code: SR1103L-105Ah
  • Availability: Pre-order
346 952 ₽

The SHTYL SR1103L online UPS kit with eight external 105 Ah batteries housed in an RTC-2401-01D2 telecommunications cabinet provides backup power to a critical load for 3 hours (at 80% load). The battery runtime at other UPS load levels is shown on the Battery runtime tab. Examples of connected load include a server, computer, telecommunications equipment or a video surveillance system.

The UPS also protects connected equipment from voltage surges and electrical interference.

The power supply operates excellently in conjunction with a generator thanks to an improved power factor corrector algorithm.

The UPS operates on the principle of double conversion of electric current, which provides:

  • voltage correction over a wide range (90-295 V) and without switching to battery;
  • instant (seamless) switching to the battery when the power fails or the voltage goes outside the operating range;
  • supplying equipment with high-accuracy voltage (±2%) with a pure sine wave.

Installation and connection

The kit is supplied partially assembled. The UPS, mounting kit, battery protection module and shelf are already pre-installed in the cabinet. You only need to place the batteries and connect them in accordance with the instructions. The connection cables are included in the scope of supply.

For load power supply, three C13 computer connectors and one C19 are used. The UPS is connected to the mains via a C20 connector.

Protection

Protection against short circuits, prolonged output overload and internal overheating is provided. The device resumes operation automatically after the cause of the electronic protection tripping is eliminated.

The UPS also has protection against:

  • impulse overvoltages (varistor – 2 kV ("case-wire"), 1 kV ("wire-wire"), response – 50 μs);
  • operating faults (when the emergency protection trips, the consumers are disconnected or seamlessly switched to the mains via the built-in bypass).

High-frequency filters protect the mains from interference in the 150 kHz - 30 MHz range and the load (from phase-to-neutral interference up to 2.5 kHz).

BPM-03-C-B battery protection module for safe connection and servicing of the battery.

Battery charging

Batteries with a capacity of 105 Ah are charged by the charger built into the UPS with a current of 2 A.

The UPS employs modern technologies to reduce charging time and extend battery service life (intelligent charging and battery charge temperature compensation), as well as algorithms that allow the battery to be disconnected at 80-85% discharge (protection against deep discharge), notify the user of battery wear and predict autonomy time (the value is displayed in the web interface; a monitoring card is required for connection).

Control panel

The main operating parameters of the product are monitored and configured using the control panel. It includes an LCD display, four function keys and five LED indicators:

  • "Status" – indicates the device operating mode;
  • "Mains" – indicates mains status;
  • "Bypass" – indicates a switch to bypass / ECO mode;
  • "Inverter" – indicates inverter operation;
  • "Battery" – shows the battery status.

The LCD display shows the input/output voltage, load percentage, battery voltage, active/apparent power and alarms.

Three battery tests can be performed (load powered from the batteries): for 10 seconds, for a set time, until fully discharged.

Monitoring tools

Local/remote monitoring is performed via a web browser or using the dedicated Shtyl Device Manager (SDM) software. This requires a board to be installed. Four board models with the following interfaces are available:

  • RS-232 (Megatec protocol) and RS-485 (Modbus RTU/SHTYL protocols);
  • USB and mini-USB;
  • Ethernet (protocols Web/SNMP/NTP/Modbus TCP/SHTYL);
  • "dry" contacts.

Expansion boards are not included in the standard scope of supply and are purchased separately.

The SR1103L UPS kit offers an excellent price/quality ratio compared with similar products from foreign vendors on the Russian power supply systems market.

  • Specifications

General specifications
Apparent power, kVA 3
Active power, kW 2,7
Form factor cabinet
Number of phases 1 to 1
Operating modes on-line, autonomous, bypass, ECO
Topology on-line (double conversion)
Country of manufacture Russia
Input characteristics
Generator compatibility yes
Input mains type single-phase three-wire (L, N, PE)
Input power factor 0.99
Limiting input voltage range, V 90-295
Maximum input current, A 20
Operating input voltage range, V 175-295 at 100% load, 155-295 at 75% load, 120-295 at 50% load
Rated input frequency, Hz 50
Rated input voltage, V 220
Soft start yes
Permissible input frequency range, Hz 45-65
Permissible deviation of the lower input voltage limit in ECO mode and for the electronic bypass, % -5, -10, -15, -20, -25 (default: -20)
Permissible deviation of the upper input voltage limit in ECO mode and for the electronic bypass, % +5, +10, +15, +20, +25 (default: +20)
Output characteristics
Crest factor 3:1
Maximum output current, A 13,5
Output power factor 0,9
Output voltage type single-phase
Rated output frequency, Hz when operating from the mains – matches the mains frequency; when operating from the battery – set by the user: 50/60
Transfer time to battery mode from on-line mode, ms 0
Output voltage total harmonic distortion, % <2.5 with linear load, <4 with non-linear load
Rated AC output voltage, V 220
Output voltage waveform pure sine wave
Efficiency in online mode, % 95
Efficiency in battery mode, % 86
Output voltage stabilisation accuracy, % ±2
Output frequency stabilisation accuracy (when operating from battery), % ±0,2
Overload capacity (when operating in on-line mode or from batteries) 101-105% – no time limit, 105-130% – for 60 s, 130-150% – for 1 s, above 150% – for 0.2 s (followed by switching to bypass)
Efficiency in bypass or ECO mode, % 99
Transfer time to battery mode from ECO mode, ms 7
Protection
Output overload electronic protection with auto-restart
Overheating electronic protection with auto-restart
Short circuit electronic protection with auto-restart
Protection against UPS failure electronic emergency protection
Protection against deep battery discharge yes
Electronic automatic bypass yes
Surge protection varistor (2 kV (case-to-wire), 1 kV (wire-to-wire), response – 50 µs)
Mains protection against high-frequency interference 150 kHz - 30 MHz
Load protection against mains interference (between phase and neutral) up to 2.5 kHz
Control panel and interfaces
Audible alarm battery mode, low voltage of internal and/or external batteries, battery disconnected/fully discharged/needs replacement, overload and UPS fault
Ethernet option (monitoring card required)
LCD display display of system operating status and main input and output parameters
LED indication status, mains, bypass, inverter, battery
RS-485 option (monitoring card required)
Indication type LCD display and LED indication
EPO pluggable screw terminal block, wire cross-section: 0.08-1.2 mm².
"Dry" contacts option (monitoring card required)
mini-USB option (monitoring card required)
RS-232 option (monitoring card required)
Function keys control of the menu displayed on the LCD, UPS configuration
USB option (monitoring card required)
Connection
Input mains IEC-320-C20
Load (output sockets) IEC-320-C13 (3 pcs.), IEC-320-C19 (1 pc.)
Reliability and performance characteristics
Cooling type forced air cooling (fan)
Degree of protection against dust and moisture IP20
Installation indoor
Operating altitude, m up to 3000 m above sea level
Relative humidity, % from 0 to 80 (non-condensing)
Service life, years at least 10
Warranty period, months 24 (12 per battery)
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Weight, kg 382,6
Overall dimensions HxWxD (unpacked), mm 600×600×1200
Batteries (battery packs)
Battery availability external
Hot-swap of built-in batteries no
Battery runtime (at 80% UPS load) 2.5 h
Rated battery voltage, V 96
Battery type sealed, maintenance-free, lead-acid
Battery service life, years up to 7 (depending on operating conditions)
Battery management functionality residual capacity determination, tests (10-second, for a specified runtime, until full discharge), deep discharge protection, charge temperature compensation
Cold start yes
Rated charge current of the built-in charger, A 2
Capacity of one 12 V battery, Ah 105
Total battery capacity, Ah 105

Write to us