The PDM-10-4TL-2AT distribution module is designed for use with the SHTYL SR1110L single-phase UPS with an output capacity of 10 kVA. The device reliably distributes power from the UPS system, generator or mains supply between single-phase loads.
The PDM-10-4TL-2AT is a 4U metal enclosure. The device is installed in the 19-inch rails of a rack or telecommunications cabinet.
The module is connected to the input mains using terminal connections. The following circuit breakers are provided for the output connection: 1xC40, 2xC20, 3xC10.
The PDM-10-4TL-2AT connects to the UPS via terminals. The connection cables are included in the scope of supply of the device.
BCR, PDU and service loads can be connected via terminal connections.
Additional functionality: IDD and ATS. Recommended circuit breaker on the external distribution board – C80, cable: 16 mm².
The choice of a specific PDM series distribution module model for a UPS model of a given capacity depends on the required functionality and the number of independent power inputs. The managers of our company or our partners will help you make the exact selection of the optimal solution.