The PDM-03-3CL-1P distribution module is used together with the SHTYL SR1103L single-phase UPS with an output power of 3 kVA. The device is designed for distribution of electrical power from the UPS system, generator or mains supply between single-phase loads.
The PDM-03-3CL-1P is a 3U metal enclosure that is installed in the 19-inch guide rails of a rack or telecommunications cabinet.
The device is connected to the input mains via terminal blocks. The following circuit breakers are used for the output connection: 1xC16, 1xC10, 2xC6, 2xC4, 2xC2.
The module is connected to the UPS using C19 and C20 connectors. The connection wires are included in the scope of supply of the device.
Additional functionality: IDD and SPD. Recommended circuit breaker on the external distribution board – C20, cable – 2.5 mm².
The choice of a specific PDM series distribution module model for a UPS model of a given capacity depends on the required functionality and the number of independent power inputs. The managers of our company or our partners will help you make the exact selection of the optimal solution.
- Specifications