The PDM-02-3CL-2AP distribution module is designed for use together with the single-phase SHTYL SR1102L UPS with an output capacity of 2 kVA.
The device is intended for distributing electricity from two power sources (from two different phases or from the mains and a generator) to single-phase loads via the UPS.
The PDM-02-3CL-2AP is a 3U metal enclosure that is installed in 19-inch rack rails or a telecommunications cabinet.
The device is connected to the input mains/generator using terminal connections (L, N, PE).
The load is connected to the module via terminals (L, N, PE). For this purpose, 6 circuit breakers are provided: 1xC10, 2xC4, 3xC2.
The PDM-01-3CL-2AP connects to the UPS via C19 and C20 connectors. The connection cables are included in the scope of delivery.
Additional functionality: input distribution device (IDD), surge protection device (SPD), voltage monitoring relay (VMR) and automatic transfer switch (ATS). Recommended circuit breaker on the external distribution board – C20, cable: 2.5 mm².
The choice of a specific PDM series distribution module model for a UPS model of a given capacity depends on the required functionality and the number of independent power inputs. The managers of our company or our partners will help you make the exact selection of the optimal solution.