The PDM-02-3CL-1S distribution module is used together with the single-phase SHTYL SR1102L UPS with an output capacity of 2 kVA.
The product is designed to distribute power from the external mains or generator to the UPS and other loads connected to the Schuko socket. The Schuko socket can be used to connect an external BCR series charger, a PDU series socket block and service consumers.
The PDM-02-3CL-1S is a 3U metal enclosure that is installed in 19-inch rack rails or a telecommunications cabinet.
The module is connected to the input mains using terminal connections (L, N, PE). The following circuit breakers are provided for the output connection: 1xC10, 2xC4, 4xC2, 1xC1.
The PDM-02-3CL-1S connects to the UPS via C19 and C20 connectors. The connection cables are included in the scope of delivery.
Additional functionality: input distribution device and Schuko socket. Recommended circuit breaker on the external distribution board – C25, cable – 4 mm².
The choice of a specific PDM series distribution module model for a UPS model of a given capacity depends on the required functionality and the number of independent power inputs. The managers of our company or our partners will help you make the exact selection of the optimal solution.