The PDM-01-3CL-1R distribution module is used together with models of single-phase UPS of the SR and STR series with a capacity of 1 kVA.
The device reliably distributes electricity from the mains or a generator to single-phase loads via the UPS.
The PDM-01-3CL-1R is a 3U metal enclosure that is installed in 19-inch rack rails or a telecommunications cabinet.
The device is connected to the input mains via terminal blocks. The following circuit breakers are used for the output connection: 1xC6, 2xC4, 3xC2 and 2xC1.
The module is connected to the UPS using C13 and C14 connectors. The connection wires are included in the scope of supply of the device.
Additional functionality: input distribution device and surge protection device. Recommended circuit breaker on the external distribution board – C16, cable – 1.5 mm².
The choice of a specific PDM series distribution module model for a UPS model of a given capacity depends on the required functionality and the number of independent power inputs. The managers of our company or our partners will help you make the exact selection of the optimal solution.