The PDM-01-3CL-1 distribution module is designed for use together with models of single-phase UPS of the SR and STR series with a capacity of 1 kVA.
The device reliably distributes electricity from the mains or a generator to single-phase loads via the UPS.
The PDM-01-3CL-1 is a 3U metal enclosure designed for installation in 19-inch rack rails or a telecommunications cabinet.
The device is connected to the input mains using terminal connections (L, N, PE).
The load is connected to the module via terminals (L, N, PE). For this purpose, 8 circuit breakers are provided: 1xC6, 2xC4, 3xC2, 2xC1.
The PDM-01-3CL-1 connects to the UPS via C13 and C14 connectors. The connection cables are included in the scope of delivery.
The module has 1 power input from the input distribution device (IDD). Recommended circuit breaker on the external distribution board – C16, cable: 1.5 mm².
The choice of a specific PDM series distribution module model for a UPS model of a given capacity depends on the required functionality and the number of independent power inputs. The managers of our company or our partners will help you make the exact selection of the optimal solution.
Connection diagrams
- Specifications