SHTYL external bypass module EBM-10-WTL-1PT

  • Brand: Shtil
  • Product Code: EBM-10-WTL-1PT
  • Availability: Pre-order
63 000 ₽

The EBM-10-WTL-1PT external bypass module is used together with single-phase ST1106L/ ST1106SL and ST1110L/ ST1110SL floor-standing UPS models with an output power of 6 and 10 kVA. The device is designed for manual, uninterrupted transfer of power for connected equipment from the UPS to the input mains for configuration, servicing or replacement of the uninterruptible power supply.

The device is installed on any flat horizontal surface.

Operating modes

The EBM-10-WTL-1PT has three operating modes, each characterised by a specific state of contacts S1, S2 and S3:

  • UPS mode (main) – the load is connected to the UPS output, the UPS power circuits are connected to the supply mains (contacts S1, S3 closed, S2 open): This is the main mode: the load is powered by the UPS inverter; in the event of an inverter fault or overload, the internal electronic automatic bypass transfers the load to the mains.
  • SERVICE mode – the load is connected to the bypass mains of the external bypass module, the UPS output is disconnected, the UPS power circuits are connected to the supply mains. The UPS runs at no load (contacts S1, S2 closed, S3 open): Service mode is used for scheduled UPS maintenance as well as for commissioning.
  • BYPASS mode – the load is connected to the bypass mains of the external bypass module, the UPS output is disconnected, the UPS power circuits are disconnected from the supply mains. The UPS is completely de-energised (contact S2 closed, S1, S3 open): Bypass mode is used to replace current-carrying components or a faulty UPS.

Connection

Terminals (L, N, PE) are used for the input connection. One power input. SPD at the input of the distribution cabinet.

Connection to the UPS is also made via terminal connections.

Circuit breakers 1xC40, 1xC32, 1xC20, 3xC10, 2xC6 are provided for the output connection.

A terminal block is provided for connecting the charger or service loads.

Control and indication

The front side of the device has:

  • bypass block diagram with LED indication showing the presence of voltage in the circuits;
  • cam switch handle for convenient switching of the device operating modes.
  • Specifications

General specifications
Form factor wall-mounted
Operating modes UPS, service, bypass
Country of manufacture Russia
Compatibility single-phase UPS ST1106SL, ST1106L, ST1110SL, ST1110L
Accessory type external bypass modules and cabinets
Number of phases of compatible UPS 1 to 1
Neutral conductor switching yes
Transfer time (to bypass mode), ms 0
Operating mode switching three-position multi-section switch
Input characteristics
Input mains type single-phase, three-wire (L, N, PE)
Rated input frequency, Hz 50
Rated input voltage, V 220
Control panel and interfaces
LED indication voltage presence, 5 pcs
Connection
Input mains terminals
Load (output sockets) circuit breakers 1xC40, 1xC32, 1xC20, 3xC10, 2xC6
Reliability and performance characteristics
Relative humidity, % from 0 to 98 (non-condensing)
Warranty period, months 24
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +40
Mechanical characteristics
Weight, kg 8
Overall dimensions HxWxD (unpacked), mm 470x470x170