The EBM-03-WTL-1PT external bypass module is used together with UPS units of the ST-TL, STR-TL and STR-TLD series with a power of 3 kVA. The device is designed for manual, uninterrupted transfer of the power supply of connected devices from the UPS to the input mains for configuration, servicing or replacement of the uninterruptible power supply.
The module is mounted on any flat vertical surface.
Operating modes
The EBM-03-WTL-1PT has three operating modes, each characterised by a specific state of contacts S1, S2 and S3:
- UPS mode (main) – the load is connected to the UPS output, the UPS power circuits are connected to the supply mains (contacts S1, S3 closed, S2 open): This is the main mode: the load is powered by the UPS inverter; in the event of an inverter fault or overload, the internal electronic automatic bypass transfers the load to the mains.
- SERVICE mode – the load is connected to the bypass mains of the external bypass module, the UPS output is disconnected, the UPS power circuits are connected to the supply mains. The UPS runs at no load (contacts S1, S2 closed, S3 open): Service mode is used for scheduled UPS maintenance as well as for commissioning.
- BYPASS mode – the load is connected to the bypass mains of the external bypass module, the UPS output is disconnected, the UPS power circuits are disconnected from the supply mains. The UPS is completely de-energised (contact S2 closed, S1, S3 open): Bypass mode is used to replace current-carrying components or a faulty UPS.
Connection
Input connections are made via terminal connections. One power input. SPD at the input of the input distribution device.
Connection to the UPS is also made via terminal connections.
For output connections, circuit breakers 1×C16, 1×C10, 2×C6, 2×C4 are provided.
A terminal block is provided for connecting the charger or service loads.
Control and indication
The front side of the module has:
- bypass block diagram with LED indication showing the presence of voltage in the circuits;
- cam switch handle for convenient switching of the device operating modes.
- Specifications