The EBM-02-WCL-1S external bypass module is used together with single-phase ST and STR series UPSs rated at 2 kVA. The device is designed for manual, no-break transfer of power to connected equipment from the UPS to the input mains for configuration, servicing or replacement of the uninterruptible power supply.
The module is mounted on any flat vertical surface.
Operating modes
The BM-02-WCL-1S has three operating modes, each characterised by a specific state of contacts S1, S2 and S3:
- UPS mode (main) – the load is connected to the UPS output, the UPS power circuits are connected to the supply mains (contacts S1, S3 closed, S2 open): This is the main mode: the load is powered by the UPS inverter; in the event of an inverter fault or overload, the internal electronic automatic bypass transfers the load to the mains.
- SERVICE mode – the load is connected to the bypass mains of the external bypass module, the UPS output is disconnected, the UPS power circuits are connected to the supply mains. The UPS runs at no load (contacts S1, S2 closed, S3 open): Service mode is used for scheduled UPS maintenance as well as for commissioning.
- BYPASS mode – the load is connected to the bypass mains of the external bypass module, the UPS output is disconnected, the UPS power circuits are disconnected from the supply mains. The UPS is completely de-energised (contact S2 closed, S1, S3 open): Bypass mode is used to replace current-carrying components or a faulty UPS.
Connection
Input connections are made via terminal connections. One power input.
Connection method to the UPS: plug-in.
Circuit breakers 1xC10, 2xC4, 3xC2 are provided for the output connections.
A Schuko socket is provided for connecting the charger or service loads.
Control and indication
The front side of the module has:
- bypass block diagram with LED indication showing the presence of voltage in the circuits;
- cam switch handle for convenient switching of the device operating modes.
- Specifications