The EBM-01-RC-PN external bypass module is used together with single-phase UPS units of the STR series with an output power of 1 kVA. The device is designed for manual, uninterrupted transfer of the load power supply from the UPS to the input mains for configuration, servicing or replacement of the uninterruptible power supply.
The EBM-01-RC-PN is mounted in the 19-inch rails of a rack or telecommunications cabinet; the unit height is 2U.
Operating modes
The EBM-01-RC-PN external bypass module has three operating modes, each characterised by a specific state of contacts S1, S2 and S3:
- UPS mode (main) – the load is connected to the UPS output, the UPS power circuits are connected to the supply mains (contacts S1, S3 closed, S2 open): This is the main mode: the load is powered by the UPS inverter; in the event of an inverter fault or overload, the internal electronic automatic bypass transfers the load to the mains.
- SERVICE mode – the load is connected to the bypass mains of the external bypass module, the UPS output is disconnected, the UPS power circuits are connected to the supply mains. The UPS runs at no load (contacts S1, S2 closed, S3 open): Service mode is used for scheduled UPS maintenance as well as for commissioning.
- BYPASS mode – the load is connected to the bypass mains of the external bypass module, the UPS output is disconnected, the UPS power circuits are disconnected from the supply mains. The UPS is completely de-energised (contact S2 closed, S1, S3 open): Bypass mode is used to replace current-carrying components or a faulty UPS.
Connection
The bypass is connected:
- to the mains via an IEC-320-C14 connector (the 'Schuko – C13' cable from the UPS is connected);
- to the UPS via an IEC-320-C13 connector (a 'C14 – C13' cable is provided);
- for powering a priority load from the UPS via an IEC-320-C14 connector (a "C14 – C13" cable is provided);
- for powering a non-priority load from the UPS via an IEC-320-C14 connector (a "C14 – C13" cable is provided).
The power cable connection connectors are configured similarly to the UPS connectors, which simplifies the connection process.
Several connectors are provided for connecting the load:
- IEC-320-C13 for priority load (3 pcs);
- Schuko socket for priority load (1 pc.);
- IEC-320-C13 for non-priority load (3 pcs);
Control and indication
The front side of the module accommodates:
- bypass block diagram with LEDs Mains, UPS Input, Bypass, UPS Output, Output;
- cam switch handle for convenient switching of the device operating modes Online, Service, Bypass.
- Specifications







