SHTYL power supply system PS24-0036 (from 300 to 900 W)

  • Brand: Shtil
  • Product Code: PS24-0036-3-0350-1U
  • Availability: In stock

The SHTYL PS24-0036 compact power supply system is designed to provide uninterruptible DC power to communication systems and any other electronic and electrical equipment with a 24 V supply voltage. The maximum output current of the device is 38.1 A, the maximum output power is 900 W.

Design features

The PS24-0036 power supply system is supplied as a 1U-high 19-inch subrack and is intended for installation in racks and cabinets. The modular design of the product and the possibility of hot-swapping the power components (rectifiers) allow flexible systems to be designed that best meet customer requirements. Detailed information on the technical specifications of the various versions of the PS24-0036 power supply system is given in the table below.

In addition to the power supplies (rectifiers), the product also includes AC input switching equipment, load protection fuses and a mains fuse, devices protecting the batteries against short circuits and deep discharges, an SHTYL PSC-200 controller for controlling the power system and organising monitoring, and a temperature sensor for measuring the temperature of the batteries. Please note that the batteries are not included in the scope of supply of the product!

Operating principle

The presented SHTYL PS24-0036 power supply system model converts 220 V AC into 24 V DC. The product can be powered from one of two sources: a 220 V, 50 Hz industrial AC mains and a DC source (battery). AC mains power is supplied to the inputs of the power supplies (rectifiers). The battery is connected in parallel with the rectifier output; switching to battery power occurs when there is no AC voltage at the rectifier inputs. The battery is switched to the output by means of a relay.

  • Advantages

General specifications
Active power, kW 0,9
Form factor rack-mounted (compact)
Country of manufacture Russia
Input characteristics
Input mains type single-phase AC mains
Input power factor 0.99 at 100% load, 0.95 at 50% load
Maximum input current, A 12.9 (when 3 power supplies (rectifiers) are installed in the product)
Rated input frequency, Hz 50
Permissible input frequency range, Hz 45-65
Operating AC input voltage range, V 90-276 (in the 90-175 V range the rectifier output power decreases linearly, down to 50% of nominal at Uin = 90 V)
Rated input AC voltage, V 220
Output characteristics
Efficiency, % no less than 90
Maximum output current, A 38.1 (with 3 power supply units (rectifiers) installed in the product, at Uin>175 V)
Output overvoltage trip threshold, V 35
Output voltage range when operating from battery, V 21-28
Output voltage type DC
RMS ripple value, mV no more than 50
Rated DC output voltage, V 24
DC output voltage range, V 20-28
Protection
Battery protection fuse rating, A 50
Load protection fuse rating, A 16
Mains fuse rating, A 20
Overheating protection with automatic recovery
PE earthing contact yes
Number of connectable loads with load current not exceeding 12 A, pcs. 2
Number of connectable loads (not protected by fuse), pcs. 1
Undervoltage or overvoltage input protection with automatic recovery
Control panel and interfaces
Ethernet yes
LED indication indication of the main product states
RS-485 yes
Temperature sensor connector yes
"Dry" contacts general alarm, battery discharge, rectifier failure, no input voltage
USB yes
Reliability and performance characteristics
Mean recovery time, h no more than 1
Service life, years no less than 20
Warranty period, months 24
Operating temperature range, °C from +5 to +50
Storage temperature range, °C from -40 to +85
Mechanical characteristics
Housing colour grey
Weight, kg no more than 8 (when 3 power supplies (rectifiers) are installed in the unit)
Rack mounting height, U 1
Overall dimensions HxWxD (unpacked), mm 44×483×350
Batteries (battery packs)
Battery availability external (option)
Battery management functionality deep discharge protection, temperature monitoring (temperature compensation)

Write to us