The electronic bypass STS7500 is used for operation in conjunction with SHTYL inverters PS 24/700C-P-1 and PS 24/700C-P-2, PS 220/700C-P-1 and PS 220/700C-P-2. The device is designed for automatic synchronous and in-phase transfer of the load from the inverter output to the mains AC supply in the event of an overload or inverter failure, and back upon return to normal operation. Transfer time – less than 10 ms.

STS7500 is designed as a 19" 1U module for installation in a 19” cabinet or rack. The front panel has two connectors for connecting synchronisation cables. The rear panel has:

  • operating mode switch;
  • terminal blocks for connecting the load and the AC mains;
  • bypass enclosure earth terminal and RS-485 connector.

The STS7500 is equipped with terminal blocks for connecting the inverter outputs.

STS7500 has two operating modes:

  • on-line – the load is continuously powered from the DC voltage source via the inverter; the load is automatically switched to the 220 V AC mains via the bypass in the event of an overload or inverter failure;
  • off-line – the load is continuously powered from the 220 V AC mains via the bypass; the load is automatically switched to inverter operation when the mains voltage fails.

The operating mode is configured at the factory and specified at ordering.

  • Specifications

General specifications
Form factor rack-mount
Country of manufacture Russia
Switched power, VA/W 9000/7500
Compatibility PS 24/700C-P-1 and PS 24/700C-P-2, PS 220/700C-P-1 and PS 220/700C-P-2 inverters
Accessory type electronic bypasses
Input characteristics
Maximum input current, A 40
Rated input frequency, Hz 50
Permissible input frequency range, Hz 48-52
Operating AC input voltage range, V 180-250
Rated input AC voltage, V 220
Lower bypass deactivation threshold, V 180 ± 2
Lower bypass activation threshold, V 195 ± 2
Upper bypass disable threshold, V 250 ± 2
Upper bypass enable threshold, V 235 ± 2
Transfer time from inverter to bypass/from bypass to inverter, ms ≤12
Control panel and interfaces
RS-485 yes
Reliability and performance characteristics
Relative humidity, % from 0 to 90 (non-condensing)
Warranty period, months 24
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -50 to +50
Mechanical characteristics
Housing colour grey
Weight, kg 4
Rack mounting height, U 1
Overall dimensions HxWxD (unpacked), mm 44x483x380
Overall dimensions HxWxD (packed), mm 65×565×530