The electronic bypass STS3000 is used for operation in conjunction with SHTYL inverters PS 24/700C-P-1 and PS 24/700C-P-2, PS 220/700C-P-1 and PS 220/700C-P-2. The device is designed for automatic synchronous and in-phase transfer of the load from the inverter output to the mains AC supply in the event of an overload or inverter failure, and back upon return to normal operation. Transfer time – less than 10 ms.
STS3000 is designed as a 19" 1U module for installation in a 19” cabinet or rack. The front panel has two connectors for connecting synchronisation cables. The rear panel has:
- operating mode switch;
- terminal blocks for connecting the load and the AC mains;
- bypass enclosure earth terminal and RS-485 connector.
For connecting inverter outputs, the STS3000 is equipped with terminal blocks.
STS3000 has two operating modes:
- on-line – the load is continuously powered from the DC voltage source via the inverter; the load is automatically switched to the 220 V AC mains via the bypass in the event of an overload or inverter failure;
- off-line – the load is continuously powered from the 220 V AC mains via the bypass; the load is automatically switched to inverter operation when the mains voltage fails.
The operating mode is configured at the factory and specified at ordering.
- Specifications