‎+7 (499) 500-24-60
Moscow, Udaltsova St., 81, bldg 2, office 6
Inverter accessories

SHTYL PS1000KM, ver.2.3 modular frame

  • Brand: Shtil
  • Product Code: PS1000KM
  • Availability: Pre-order

The PS1000KM,ver.2.3 modular frame is designed for installing one SHTYL PSC-300.03.02 controller (in a special slot) and up to 2 SHTYL PS48-60/1000K or PS48-60/1000K(I), or PS48-60/1000K,ver.2, or PS48-60/1000K(I),ver.2 inverters and connecting them to an input 48 V or 60 V DC voltage, an input 230 V 50 Hz AC voltage and the load.

The frame is made as a complete module in a metal enclosure 1U high and 19’’ wide and is intended for installation in 19-inch cabinets and racks. Power from a DC voltage source is connected to the "-" and "+" terminals located on the rear side of the frame.

AC input mains 230 V and load – via PE, N, L terminals. Input overvoltage and surge protection is provided. Up to 7 PS1000K frames can be connected in parallel to the PS1000KM,ver.2.3 frame.

The product supports monitoring of the installed inverters via dry contacts, as well as via a SHTYL PSC-300.03.02 controller, which provides Ethernet-based inverter monitoring (including via the SNMP protocol).

Please note!

The PSC-300.03.02 controller is not included in the price and scope of supply of the PS1000KM,ver.2.3 modular frame and is purchased as a separate item.

  • Specifications

General specifications
Form factor rack-mount
Country of manufacture Russia
Compatibility SHTYL PS48-60/1000K(I),ver.2 inverter, SHTYL PS48-60/1000K,ver.2 inverter, SHTYL STS12000(I) electronic bypass, SHTYL PS1000K modular frame
Accessory type modular frames (subracks)
Maximum number of inverters per frame, pcs. 2
Input characteristics
Limiting input voltage range, V 90-310
Rated input frequency, Hz 50
Operating AC input voltage range, V 145-285
Rated input AC voltage, V 230
Operating input DC voltage range, V 40,5-72
Rated input DC voltage, V 48-60
Output characteristics
Rated AC output voltage, V 230
Rated output current, A 9.08 (with the full number of inverters installed)
Protection
Surge protection yes
Control panel and interfaces
LCD display on the controller
LED indication on the controller
Parallel operation up to 8 pcs. (with PS1000K modular frame)
RS-485 yes (internal)
"Dry" contacts yes
Modbus RTU option
Connection
Load (output sockets) terminals (L, N, PE)
DC input mains terminals (+,-)
AC input mains ~ 220 V 50 Hz terminals (L, N, PE)
Reliability and performance characteristics
Relative humidity, % from 0 to 90 (non-condensing)
Warranty period, months 24
Operating temperature range, °C from +5 to +40
Storage temperature range, °C from -40 to +85
Mechanical characteristics
Weight, kg 7
Rack mounting height, U 1
Overall dimensions HxWxD (unpacked), mm 45×483×420

Write to us