MWM

MWM TCG 2020 V20 — 2,000 kW

  • Brand: MWM
  • Product Code: TCG 2020 V20
  • Availability: Pre-order

MWM TCG 2020 V20 is a 2,000 kW gas generator set built on the MWM TCG 2020 engine. 20 cylinders, 1,500 rpm.

Electrical efficiency 43.7 %; total efficiency with heat recovery 87.0 %.

Fuel: natural gas, biogas. The unit is used for prime and standby power at industrial sites, in municipal energy and for cogeneration: combined generation of electricity and heat.

Supply, installation, commissioning and service — LEVRUS. Scope, lead time and price are defined by the project.

Factory sheet data (natural gas, NOx 500 mg/Nm³, 50 Hz)

Electrical output, kW (100 / 75 / 50% load)2,000 / 1,500 / 1,000
Engine power per ISO 3046, kW2,055 / 1,543 / 1,035
Electrical efficiency, %43.7 / 42.4 / 40.2
Thermal efficiency (exhaust cooled to 120 °C), %43.3 / 44.5 / 46.7
Total efficiency, %87.0 / 86.9 / 86.9
Fuel energy input, kW4,581 / 3,538 / 2,488
Gas flow at 100%, m³/h (calculated: energy ÷ heating value 10.5 kWh/m³)436
Jacket water heat, kW978 / 781 / 549
Intercooler (LT) heat, kW172 / 123 / 73
Exhaust heat cooled to 120 °C, kW1,005 / 795 / 612
Engine / generator radiation at 100%, kW70 / 55
Exhaust temperature, °C424 / 435 / 468
Exhaust mass flow (wet), kg/h10,741 / 8,185 / 5,676
Combustion air flow, kg/h10,402 / 7,923 / 5,492
Mean effective pressure, bar18.6 / 13.9 / 9.4
Bore × stroke, mm170 × 195
Displacement, dm³88.5
Compression ratio13.5:1
Methane number / NOx emission80 / 500 mg/Nm³
Exhaust back pressure, mbar (min / max)30 / 50
Noise at 1 m, dB(A): exhaust / engine casing (no enclosure)123 ± 2.5 / 112 ± 1.0
Dry weight engine / genset, kg7,800 / 18,200
Alternator on the sheetMarelli MJB 560 LA 4 or equal

Source: MWM data sheet TCG 2020 V20, natural gas, NOx 500 mg/Nm³, dated 11.02.2010. Tolerance on heat rejection ±8%, on fuel consumption +5%. The sheet dates from 2009–2010: weight and dimensions depend on the alternator, and the efficiency at the top of the page (from the MWM brochure) may differ from the sheet by tenths of a percent. Ask the manufacturer for a current offer for a project.

Gas and NOx variants in the data sheets

VariantOutput, kWElec. eff., %Total eff., %Sheet date
natural gas, NOx 5002,00043.787.011.02.2010
natural gas, NOx 250 (10.5 kV generator, 2009 sheet)2,00442.286.820.08.2009
biogas, NOx 5002,00042.085.711.02.2010

Output and efficiency are at 100% load. The NOx 250 mg/Nm³ variant gives lower efficiency at the same output; biogas and gas of another composition need a separate calculation.


Gas generator set
Electrical output, kW 2 000
Electrical efficiency, % 43,7
Exhaust heat, kW 1 005
Fuel energy input, kW 4 581
Total efficiency with heat recovery, % 87,0
Fuel natural gas, biogas
Speed, rpm 1 500
Number of cylinders 20
Displacement, l 88,5
Bore / stroke, mm 170 / 195
NOx emission, mg/Nm³ 500
Execution open or containerised