Cummins C1540 N5C — 1,540 kW (1,500 rpm)

  • Brand: Cummins
  • Product Code: C1540 N5C
  • Availability: Pre-order

Cummins C1540 N5C is a gas generator set built on the QSV91G engine, 50 Hz, 1,500 rpm. Electrical output 1,540 kW (1,925 kVA at 0.8 power factor).

Engine: 18 cylinders, V-type, 180 × 200 mm bore and stroke, 91.6 litres displacement, 14.0 bar BMEP, compression ratio 12:1 / 11,4:1 / 10,5:1. Electrical efficiency 38.3%, overall efficiency 39.4%. Fuel consumption at full load is 423 m³/h at 0,25–6.0 bar gas supply pressure; minimum methane number without derating is 52.

Heat balance: 485 kW to the high-temperature circuit, 458 kW to the low-temperature circuit and 1,050 kW in the exhaust at 105 °C, about 1,993 kW of recoverable heat in total. Exhaust temperature 507 °C, exhaust flow 2.44 kg/s. These figures are what a CHP design is built on.

Dimensions 5,603 × 1,720 × 3,136 mm, wet weight 17,057 kg, oil capacity 560 litres, oil consumption < 0.5 g/kWh. Control panel: PowerCommand 3.3. Time between overhauls 30,000 hours, major overhaul interval 60,000 hours.

Data from the Cummins technical table for C-series 50 Hz sets at 1,500 rpm. Price and lead time on request: the scope depends on the power export scheme, heat recovery arrangement and protection requirements.

The overall height of 3.14 m exceeds the internal height of a standard container, so the set travels on an open platform or in a purpose-built module; for indoor installation the same figure sets the door and hall height requirements.

Gas requirement: methane number not below 52 without derating, inlet pressure 0,25–6.0 bar, and calorific value within the design range. Where methane number is lower, the set loses output and the duty has to be agreed with the factory rather than adjusted on site: on low-methane gas knock limits load before it shows up in fuel consumption.

Builds and what they change

Each C-series model is built in several variants. The difference is not the rating but the acceptable gas composition, the NOx level and the high-temperature circuit temperature. The build decides whether the set delivers full output on your gas and which heat grade you can recover.

BuildFuelMin. methane numberNOx, mg/Nm³HT/LT, °CNote
D-3290associated petroleum gas5250090/40CR 10.5:1
D-3291natural gas6050095/50
D-3292natural gas5635095/50
D-3293natural gas63500110/50
D-3294natural gas59350110/50
D-3295natural gas7050095/50
D-3296natural gas6635095/50
D-3297natural gas73500110/50
D-3298natural gas69350110/50
D-3474low-calorific gas—350110/50landfill gas, coal mine methane, biogas

Methane number is the gas knock resistance rated under the AVL method. The lower it is, the earlier load has to be limited, which is why natural-gas and low-calorific-gas builds differ in compression ratio rather than only in controller settings.

NOx comes in three levels: 250, 350 and 500 mg/Nm³, set by the emission permit for the site. For the same gas the 350 mg/Nm³ build usually asks for a different methane number than the 500 mg/Nm³ build, as the table shows.

HT/LT are the jacket-water temperatures in the high- and low-temperature circuits. A 110/50 °C circuit supplies heat usable by a wider set of consumers than 95/50 °C, but needs different heat-exchange equipment; the choice follows the heat scheme, not spare margin.

The build is agreed per project: gas, emission limits, heat recovery scheme. Price and lead time depend on the code, so a request is best started from the gas analysis and the emission permit rather than from the kW figure.

Dimensions and weight are taken from Cummins data sheet S-1463g (11/08) for a set with standard features; other configurations (radiator, silencer, container) differ. Room layout and transport both need the drawing of the specific build.

How to read the designation, how builds differ by methane number and NOx, and how to size heat recovery — see Cummins C-series 50 Hz: choosing the build.


Gas generator set
Electrical output, kW 1540
Apparent power, kVA 1925
Fuel natural gas
Frequency, Hz 50
Speed, rpm 1 500
Voltage, V 400 / 6 300 / 10 500
Weight, kg 17 057
Number of cylinders 18
Displacement, l 91,6
Bore / stroke, mm 180 × 200
Dimensions (L×W×H), mm 5 603 × 1 720 × 3 136
NOx emission, mg/Nm³ 350 / 500
Main
Amount of heat dissipated, kW 255
Amount of heat in exhaust at t_out=105ºC 1050
Amount of heat in high-temperature circuit, kW 485
Amount of heat in low-temperature circuit, kW 458
Compression ratios 12:1 / 11,4:1 / 10,5:1
Control panel type PowerCommand 3.3
Electrical efficiency, % 38,3
Engine model QSV91G
Exhaust gas temperature, °C 507
Fuel consumption at 100 % load, m3/hour 423
Gas supply pressure, Bar 0,25–6,0
Mechanical efficiency, % 39,4
Minimum methane number without power derating 52–73
Oil consumption, g/kW.h < 0,5
Oil system capacity, l 560