‎+7 (499) 500-24-60
Moscow, Udaltsova St., 81, bldg 2, office 6
RU|EN
0

Cummins C400D5E — 288 kW (360 kVA), diesel — archive

  • Brand: Cummins
  • Product Code: Cummins C400D5E
  • Availability: Pre-order

This model is discontinued. It is absent from the current Cummins 50 Hz range cards (2025) and its page on the manufacturer website is no longer available. The card is kept for reference by owners of sets bought earlier. Closest models in the current range: C400D5 (QSG12-G1) and C400D5EB (QSZ13-G7). For spare parts and service please quote the genset serial number.

Cummins C400D5E diesel generator set, 50 Hz: 320 kW / 400 kVA standby and 288 kW / 360 kVA prime. Engine QSX15G8, alternator HC4F, factory panel code 46055 for large sets; the function set is confirmed by the build data sheet.

Designation: C is the Cummins series, 400 the frame size, D diesel and 5 50 Hz. The QSX15G8 engine is 6-cylinder 15 litre, electronically managed.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 320 and 288 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The factory panel code 46055 for large sets; the function set is confirmed by the build data sheet determines which protections and interfaces are available.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 15). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm137 × 169
Compression ratio17:1
BMEP, kPa (standby / prime)2675 / 2371
Piston speed, m/s8.4
Engine oil capacity, L91
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)29.49 / 47.69 / 67.06 / 85.65
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)26.00 / 44.20 / 61.25 / 78.30
Combustion air, m³/min (standby / prime)36.27 / 32.5
Exhaust flow at rated load, m³/min (standby / prime)82.2 / 75.3
Exhaust temperature, °C (standby / prime)515 / 488
Max exhaust back pressure, kPa10.2
Radiator fan load, kW16
Heat rejected to room, BTU/min (standby / prime)16 700 / 13 700
Dimensions L × W × H, mm, open set3 427 × 1 500 × 2 066
Dimensions L × W × H, mm, canopy5 106 × 1 553 × 2 447
Dry weight, kg (open / canopy)3 744 / 5 049
Wet weight, kg (open / canopy)4 582 / 5 887

Source: Cummins specification sheet DS346-CPGK-RevAR. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.

Noise

Enclosed sound power level LWA, dB(A)97
Sound pressure at 7 m, enclosed, dB(A) (75 / 100 / 110 % load)69 / 70 / 70
Sound pressure at 15 m, enclosed, dB(A) (75 / 100 / 110 % load)64 / 65 / 65
Open set average sound pressure at 1 m, dB(A) (at 100 % load)101
Open set sound power level, dB(A) (at 100 % load)117

Source: Cummins noise data sheets ND50-CS550-RevF / ND50-OS550-RevG. Factory values measured per ISO 8528-10 and Directive 2000/14/EC; levels at other distances and inside a room are calculated separately.


Diesel generator set
Prime power, kW 288
Standby power, kW 320
Prime power, kVA 360
Standby power, kVA 400
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 137 × 169
Dimensions (L×W×H), mm 3 427×1 500×2 066
Dry weight, kg 3744
Weight, kg 4582
Fuel consumption 85.65 L/h (full load, standby)
Engine QSX15G8
Generator model HC4F
Canopy no
EU/TAL 15
Main
Control panel type 46055

Write to us

We will reply to info@levrus.ru shortly