Cummins C900D5 — 656 kW (820 kVA), diesel

  • Brand: Cummins
  • Product Code: Cummins C900D5
  • Availability: Pre-order

Cummins C900D5 diesel generator set, 50 Hz: 720 kW / 900 kVA standby and 656 kW / 820 kVA prime. Engine QSK23G3, alternator HC6H, PowerCommand 2100, extended panel.

Designation: C is the Cummins series, 900 the frame size, D diesel and 5 50 Hz. The QSK23G3 engine is 6-cylinder 23 litre, electronically managed.

The two ratings are different duty classes, not a margin. Standby allows variable load for a limited number of hours per year with no overload; prime allows continuous operation with a 10 % overload for one hour in twelve. The gap between 720 and 656 kW is exactly those 10 %, and the choice follows the way the site will run, not the larger figure: using a standby rating as prime voids the factory warranty.

The 100–700 kW class carries most standby projects. What matters here is not the nameplate but the dynamics: starting of pumps and fans, load acceptance from a UPS and behaviour on step load. The PowerCommand 2100 determines which protections and interfaces are available.

Data from the factory table: standby and prime ratings, engine, alternator, panel, canopy availability (EU/TAL — 92). Price and lead time on request: the scope depends on the power export scheme, the ATS type and protection requirements.

Factory data sheet

Bore × stroke, mm170 × 170
Compression ratio16:1
BMEP, kPa (standby / prime)2675 / 2441
Piston speed, m/s8.6
Engine oil capacity, L95
Fuel consumption, L/h, standby (¼ / ½ / ¾ / full)50 / 92 / 134 / 178
Fuel consumption, L/h, prime (¼ / ½ / ¾ / full)46 / 85 / 121 / 161
Combustion air, m³/min (standby / prime)53.3 / 48.7
Exhaust flow at rated load, m³/min (standby / prime)147.8 / 135.6
Exhaust temperature, °C (standby / prime)543 / 532
Max exhaust back pressure, kPa10.1
Radiator fan load, kW16
Heat rejected to room, BTU/min (standby / prime)20 965 / 19 196
Dimensions L × W × H, mm, open set4 266 × 1 879 × 2 052
Dry weight, kg6 539
Wet weight, kg6 680

Source: Cummins specification sheet DS33-CPGK-RevCR; Layout 23077 QSK23. Figures are factory values; request the current outline drawing for your exact configuration, because weight and size change with radiator, silencer, tank and canopy.


Diesel generator set
Prime power, kW 656
Standby power, kW 720
Prime power, kVA 820
Standby power, kVA 900
Frequency, Hz 50
Speed, rpm 1 500
Bore × stroke, mm 170 × 170
Dimensions (L×W×H), mm 4 266×1 879×2 052
Dry weight, kg 6539
Weight, kg 6680
Fuel consumption 178 L/h (full load, standby)
Engine QSK23G3
Generator model HC6H
Canopy no
EU/TAL 92
Main
Control panel type 2100

Write to us

We will reply to info@levrus.ru shortly